DS1200-3-002

Manufacturer Part Number
DS1200-3-002
Description
POWER SUPPLY AC/DC 12V 1200W
Manufacturer
Emerson Network Power
Series
DS1200r
Datasheets

Specifications of DS1200-3-002

Voltage - Output
12V
Number Of Outputs
1
Power (watts)
1200W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
180 ~ 264VAC
Mounting Type
Chassis Mount
1st Output
12 VDC @ 100A
Size / Dimension
11" L x 3.2" W x 1.57" H (279.4mm x 81.3mm x 39.9mm)
Power (watts) - Rated
1200W
Operating Temperature
-10°C ~ 50°C
Efficiency
91%
Approvals
CB, CE, cUL, EN, NEMKO, UL
Line Regulation
±5%
Load Regulation
±5%
Input Voltage
90 to 264V
Output Voltage
12V
Input Frequency
47 to 63Hz
Screening Level
Commercial
Operating Temperature Min Deg. C
-10C
Operating Temperature Max Deg. C
50C
Mounting Style
Desktop
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
454-1271
DS1200-3 Series Supported PMBus
Command
Code
5Ch
5Eh
5Fh
60h
61h
64h
78h
79h
Command Name
IIN-OC-FAULT_RESPONSE
POWER_GOOD_ON
POWER_GOOD_OFF
TON_DELAY
TON_RISE
TOFF_DELAY
STATUS_BYTE
b7 – BUSY
b6 – OFF
b5 – VOUT_OV
b4 – IOUT_OC
b3 - VIN_UV
b2 - TEMPERATURE
b1 – CML
b0 – NONE OF THE ABOVE
STATUS_WORD
b15 – VOUT
b14 – IOUT/POUT
b13 – INPUT
b12 – MFR
b11 – POWER_GOOD#
b10 - FANS
b9 – OTHER
b8 – UKNOWN
b7 – BUSY
b6 – OFF
b5 – VOUT_OV
b4 – IOUT_OC
b3 - VIN_UV
b2 – TEMPERATURE
b1 – CML
b0 – NONE_OF_THE_ABOVE
TM
Command List:
Default Value
FC03
FC08
C300
9804
8813
00
Access
Type
R
R
R
R
R
R
R
R
Bytes
Data
1
2
2
2
2
2
1
2
Format
Direct
Direct
Direct
Direct
Direct
Data
Turn PSU OFF. cleared upon AC recycle.
Sets the threshold by which the Power Good
signal is asserted. (11.76V)
Sets the threshold by which the Power Good
signal is de-asserted. (10.2V)
Sets the time (sec), from start condition (Power
ON) until the output starts to rise. (2sec)
Sets the time (ms), for the output rises from 0 to
regulation. (50ms)
Sets the time (ms), from a stop condition (Power
OFF) until the output starts to drop (converter
OFF).(23ms)
Returns the summary of critical faults
A fault was declared because the device was
busy and unable to respond.
Unit is OFF
Output over-voltage fault has occurred
Output over-current fault has occurred
An input under--voltage fault has occurred
A temperature fault or warning has occurred
A communication, memory or logic fault has
occurred.
A Fault Warning not listed in bits[7:1] has
occurred.
Summary of units Fault and warning status.
An output voltage fault or warning has occurred
An Output current or power fault or warning has
occurred.
An input voltage, current or power fault or
warning as occurred.
A manufacturer specific fault or warning has
occurred.
The POWER_GOOD signal is de-asserted
A fan or airflow fault or warning has occurred.
A bit in STATUS_OTHER is set.
A fault type not given in bits [15:1] of the
STATUS_WORD has been detected.
A fault was declared because the device was
busy and unable to respond.
Unit is OFF
Output over-voltage fault has occurred
Output over-current fault has occurred
An input under-voltage fault has occurred
A temperature fault or warning has occurred
A communication, memory or logic fault has
occurred.
A fault or warning not listed in bits[7:1] of this
byte has occurred.
Description
Rev.10.03.30_#0.1
DS1200-3 Series
Page 52

Related parts for DS1200-3-002