4435.0006 Schurter Inc, 4435.0006 Datasheet

no-image

4435.0006

Manufacturer Part Number
4435.0006
Description
CIRC BREAKER/RED ROCKER SP 5A
Manufacturer
Schurter Inc
Series
TA35r
Type
Thermalr
Datasheets

Specifications of 4435.0006

Breaker Type
Thermal
Voltage
32VDC, 240VAC
Current - Trip (it)
5A
Number Of Poles
1
Actuator Type
Rocker
Mounting Type
Panel Mount
Alt Mfr.s Type
TA35-CFTRF050C0
Brand/series
TA35 Series
Current, Rating
5 A
Dimensions
36mmLx17.5mmWx44.1mmH
Mounting Hole Size
14.5x34 mm
Termination
Quick Connect
Voltage, Rating
240/32 VAC/VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
TA35-CFTRF050C0
2
Thermal Circuit Breaker, rocker actuated, 1-, 2- or 3-pole
Description
– Thermal circuit breaker 1-, 2- or 3-pole
– Supplementary protector for general industrial use
– Positively trip-free release
– Snap-in mounting
– Version with illuminated rocker
– Different rocker colours
– Protection cover for IP65
– «Dead-Man»-version (Momentary switch)
Standards
– IEC 60934
– UL 1077
– CSA C22.2 235
TeChniCAl DATA
Rated voltage U
Rated current I
Conditional short
circuit I
Degree of protection
Dielectric strength
Insulation resistance
Endurance (typical)
TA35 1-pole
nc
n
e
1-pole
2-pole
3-pole
1- / 2-pole
3-pole
1- / 2-pole, AC 240 V
3-pole, AC 415 V
Accessible range
Terminal side
50 Hz
Impulse 1.2/50 µs
DC 500 V
Mechanical
AC: 1 x I
DC: 1 x I
n
n
, L/R = 2…3ms 50’000 cycles
, cos phi 0.6
circuit breakers
AC 240 V / 50/60 Hz
DC 32 V
AC 240 V / 50/60 Hz
DC 60 V
AC 415 Y/240 V / 50/60 Hz
0.05 – 20 A
0.05 – 12 A
0.05…20 A: 2000 A, SC (C1)
0.05…12 A: 2000 A
IP 40
IP 00
> 2500 V
> 4000 V
> 100 MOhm
50’000 cycles
50’000 cycles
TA35 2-pole
circuit breakers
Applications
– Power tools
– Industrial equipment
– Equipment for building construction
– Medical equipment
– Cleaning equipment
– Power generators
– Commercial and household kitchen appliances
Overload
Admissible ambient
air temperature
Resistance to vibration
Shock resistance
Type of tripping
Weight
Max. switching capacity 1-, 2-pole
for switch only types
(without bimetal)
IEC 60934
UL 1077
IEC 60068-2-6, Test Tc
IEC 60068-2-27, Test Ea 30 G / 18 ms
1-pole
2-pole
3-pole
3-pole
TA35 3-pole
min. 40 cycles @ 6 x I
cos phi 0.6
min. 50 cycles @ 1.5 x I
cos phi 0.75 (OLØ)
–30 °C to +60 °C
10…60 Hz: ±0.75 mm
60…500 Hz: 10 G
Thermal positively trip free
19 g
32 g
45 g
20 A
12 A
n
,
n
,

Related parts for 4435.0006

4435.0006 Summary of contents

Page 1

... Type of tripping > 2500 V Weight > 4000 V > 100 MOhm Max. switching capacity 1-, 2-pole 50’000 cycles for switch only types 50’000 cycles (without bimetal) circuit breakers TA35 3-pole IEC 60934 min. 40 cycles @ cos phi 0.6 UL 1077 min. 50 cycles @ 1 cos phi 0.75 (OLØ) –30 °C to +60 °C IEC 60068-2-6, Test Tc 10… ...

Page 2

... VDE IEC 60934 4 circuit breakers Rated currents 0.05…20 A 0.05…20 A 0.05…12 A 0.05…20 A 0.05…20 A 0.05…12 A 0.05…20 A 0.05…20 A 0.05…12 A circuit breakers Rated voltage AC Rated voltage DC 240 240 415 Y/240 V — 240 240 415 Y/240 V — 240 240 415 Y/240 V ...

Page 3

CoDe Number of switched poles Number of protected poles Switch without CFC Illumination Switch illuminated 415 V 240 V CF2 CF4 120 CF7 12 V CF8 CF9 5 V Momentary without CgC ...

Page 4

... Quick connect terminal Quick connect terminal IEC 61210 A6.3-0.8 IEC 61210 A6.3-0.8 40.5 31.9 Label P1 11 2.3 34.5 37.4 Quick connect terminal IEC 61210 A6.3-0.8 circuit breakers +0.2 +0.2 14.5 14 +0.3 Panel thickness 1.0…4 +0.2 +0 +0.3 11 6.1 Panel thickness 1.0…4 ...

Related keywords