2-6500-P10-10A E-T-A, 2-6500-P10-10A Datasheet

no-image

2-6500-P10-10A

Manufacturer Part Number
2-6500-P10-10A
Description
CONTROL MOTOR PROTECTION 10A
Manufacturer
E-T-A
Series
2-6500r
Datasheet

Specifications of 2-6500-P10-10A

Breaker Type
Thermal
Voltage
28VDC, 250VAC
Current - Trip (it)
10A
Number Of Poles
1
Actuator Type
Automatic Reset
Mounting Type
Panel Mount
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
2-6500-P10-10AMP
Q1560656
Bimetal operated single pole motor protection control with automatic
reset actuation, small physical size, reliable snap-action mechanism.
Caution: In specifying this product, care should be taken to ensure that
automatic motor re-start does not represent a safety hazard.
Motors, transformers, extra low voltage wiring.
Type No.
2-6500
2-6500 - P10 - ... - 6 A
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
Current
rating (A)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
1
1.2
1.5
1.8
Authority
UL
Issue B
Description
Typical applications
Ordering information
Standard current ratings and typical internal resistance values
Approvals
surface type with flange
Terminal design
P10
blade terminals 6.3-0.8 (QC .250)
Shunt terminal (optional)
A3
Internal
resistance (Ω)
140
47.5
20.5
11.4
7.25
5.35
3.8
2.95
1.92
1.32
0.85
0.59
blade terminals or solder terminals; max. load 5 A
Current ratings
0.1...10 A
Motor Protection Control 2-6500-...
Voltage rating
AC 250 V; DC 28 V
ordering example
Current
rating (A)
2
2.5
3
3.5
4
4.5
5
6
7
8
9
10
Current rating
0.1...10 A
Internal
resistance (Ω)
0.47
0.33
0.212
0.155
0.107
0.095
0.072
0.054
0.032
0.02
< 0.02
< 0.02
www.e-t-a.com
Dielectric strength
Reset time at 23 °C
Degree of protection
Shock
Corrosion
Humidity
Voltage rating
Current ratings
Typical life
Ambient temperature
Insulation co-ordination
(IEC 60664 and 60664 A)
(IEC 60664 and 60664A)
Insulation resistance
Interrupting capacity
(IEC 60529/DIN 40050)
Vibration
Mass
Technical data
AC 250 V (50/60 Hz); DC 28 V
0.1...10 A (up to 15 A upon request)
100,000 operations at 2 x I
Protection is ensured for 18 days of
continuous locked rotor condition with
I
(unsupervised duty)
-10...+60 °C (-10...+140 °F)
rated impulse
withstand voltage degree
2.5 kV
test voltage AC 2,000 V
> 100 MΩ (DC 500 V)
8 x I
≥ 30 sec
≤ 70 sec
housing IP30
terminal area IP00
5 g (57-500 Hz) ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
15 g (11 ms)
test to IEC 60068-2-27, test Ea
48 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
approx. 20 g
2-6500-...
k
≤ 6 x I
N
(co-co-co)
N
, max. 30 A
pollution
3
N
1 - 109
1

Related parts for 2-6500-P10-10A

2-6500-P10-10A Summary of contents

Page 1

... A3 blade terminals or solder terminals; max. load 5 A Current ratings 0.1...10 A 2-6500 - P10 - ... - 6 A ordering example The exact part number required can be built up from the table of choices shown above. Ordering references for optional features should be omitted if not required. Standard current ratings and typical internal resistance values ...

Page 2

... Errors and omissions excepted. www.e-t-a.com 10000 1000 100 … times rated current +14 +32 +50 +73.4 +861 +104 +122 +140 °C -10 0 +10 +23 +30 +40 +50 0.84 0. 1.08 1.16 1.24 inch +60 Issue B ...

Related keywords