4420.0236 Schurter Inc, 4420.0236 Datasheet

no-image

4420.0236

Manufacturer Part Number
4420.0236
Description
CIRCUIT BRKR THERMAL 40.0A 2POLE
Manufacturer
Schurter Inc
Series
AS168r
Type
Thermal/Magneticr
Datasheets

Specifications of 4420.0236

Breaker Type
Thermal-Magnetic
Voltage
65VDC, 277/480VAC
Current - Trip (it)
40A
Number Of Poles
2
Actuator Type
Lever
Mounting Type
DIN Rail
Alt Mfr.s Type
AS168X-CB2G040
Brand/series
AS168 Series
Current, Rating
4 A
Standards
VDE EN 60934, UL 1077, CSA 22.2 235
Termination
Screw
Voltage, Rating
480 VAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
CBE AS168X-CB2G040
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR
Product description
The AS168X is a thermal magnetic high performance CBE to IEC 934
and a «supplementary protector» to UL 1077. It is capable of drasti-
cally limiting the «let-through energy» in case of short circuit interrup-
tions. The series is available in units from one to four poles for use in
AC and DC circuits. Multipole devices are connected internally and at
the handle for simultaneous operation. This applies also to combina-
tions with the switched neutral pole. Well designed screw type term-
inals at line and load side are provided for safe and easy connection
to line and load. They accept #16 to 4 AWG / 1,5 to 25 mm
The AS168X is suitable as supplementary protector under
UL 1077 / EN 60934 or as Manual Motor Controller according
UL 508 / CSA 22.2 14. Thus the Breaker has a high versatility
and is suitable for many functions:
• Motor overload protection (thermal and magnetic)
• Motor starting across-the-line (direct-on-line)
• Motor starting with motor disconnect (cos phi 0,4 – 0,5)
• Motor group installation (short capacity 5 kA)
• Control circuits
Accessories
• Auxiliary contact module
• Signal contact module
• Relay trip module
• Switched neutral pole (factory assembled)
Features
• Excellent short circuit performance (up to 10 kA)
• High limits of discrimination (due to energy limitation)
• Wide choice of characteristics (Adaptability)
• Availability of AC and DC in the same frame size
• Compact, «finger safe» design
• Ease installation (on DIN rail)
Applications
• Industrial machines
• Automation
• Aircondition, ventilation
• Transformers
• Power supplies
• Telecom systems
• Computer systems
• Test systems
• Medical equipments
Each auxiliary contact module contains one contact,
either normally open or normally closed.
Signal contact modules are linked internally with the protected
poles but not linked at the handles.
Contacts are actuated by a fault condition at the protected poles,
not by the manual operation of the CBE.
The relay trip module can be used for remote tripping of the
adjacent poles by applying a voltage to the module’s terminal.
This module allows to automatically open the neutral line when
the protected poles have been tripped.
2
.
www.schurterinc.com
AS168X
123

Related parts for 4420.0236

4420.0236 Summary of contents

Page 1

MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR Product description The AS168X is a thermal magnetic high performance CBE to IEC 934 and a «supplementary protector» 1077 capable of drasti- cally limiting the «let-through energy» in case of ...

Page 2

MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR Effect of ambient temperature AC-breakers are calibrated for an ambient temperature of +40°C, DC-breakers for +23°C. To determine the rated current for a lower or higher ambient temperature, use a correction factor from the ...

Page 3

MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR Tripping characteristic DF 1hr 1000s 100s 10s 1s 0,1s 10ms 1ms 0,1ms 1 10 100 1000 Multiple of rated current ( Technical data Pole : Rated voltage U ...

Page 4

MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR Technical data (continued) Add-on modules Auxiliary contact H1 & H2 and Signal contact S1 & S2 Functional auxiliary contact module Functional signal contact Relay trip module Function of relay trip module General data Dielectric ...

Page 5

MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR Approvals AC versions EN 60934 Poles Characteristic/ Volt 420/240 420/240 0 420/240 0 ...

Page 6

MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR Conversion table Ampere rating – Horsepower rating Voltage Rating: One pole: Two pole: Three pole: HP-Rating: 1 phase (1 pole & 2 pole): AS168X-CB MOTOR NAMEPLATE Rated Current FLA Starting/ (See Note #1) Rating ...

Page 7

MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR Order code AS168X – 200 N AS168X – ACB S2 Basic type Thermal magnetic high performance circuit breaker Number of poles Tripping characteristics Thermal Magnetic F 1.0 ...

Page 8

MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR DIN rail mounting AS168X-CB1… 1 DIN rail EN 50022 Max. torque Wire crosssection Max. torque 1.5… 2 …25 mm 3.1 Nm AWG #16...8 22 ...

Page 9

MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR Schematic diagrams AS168X-CB1… AS168X-CB1…N AS168X-CB1… AS168X-CB1… AS168X-ACBS1 AS168X-ACBS2 Accessories AS168X-ACBLOA Lockout attachment XFPB Frontpanel bracket AS168X-CB1… AS168X-CB1… AS168X-ACBH1 AS168X-ACBH2 AS168X-CB1… AS168X-ACBA. Part Number # of Poles "A" "B" XFPB XFPB-2 2 ...