IEGH66-1-62-20.0-21-V Sensata Technologies/Airpax, IEGH66-1-62-20.0-21-V Datasheet - Page 11

no-image

IEGH66-1-62-20.0-21-V

Manufacturer Part Number
IEGH66-1-62-20.0-21-V
Description
CIRCUIT BREAKER HYMAG DP 20A
Manufacturer
Sensata Technologies/Airpax
Series
IEGr
Datasheet

Specifications of IEGH66-1-62-20.0-21-V

Breaker Type
Hydraulic-Magnetic
Voltage
80VDC, 250VAC
Current - Trip (it)
20A
Number Of Poles
2
Actuator Type
Toggle
Mounting Type
Panel Mount
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
Q4528480
http://airpax.sensata.com/
30.1 to 50
.05 to 30
MAIN TERMINAL TYPES
Rating
CONFIGURATIONS
Series Trip
The most popular configuration for magnetic protectors is the
series trip where the sensing coil and contacts are in series
with the load being protected. The handle position conveniently
indicates circuit status. In addition to providing conventional
overcurrent protection, it’s simultaneously used as an on-off
switch.
Shunt Trip
The shunt trip is designed for controlling two separate loads with
one assembly. The control is established by providing overload
protection for the critical load. When the current through this
load becomes excessive and reaches the trip point, the protector
will open and remove power from both loads simultaneously. The
total current rating of both loads must not exceed the maximum
contact rating.
Auxiliary Switch (Applies to Series Trip Only)
This is furnished as an integral part of a series pole in single or
multi-pole assemblies. Isolated electrically from the protector’s
circuit, the switch works in unison with the power contacts
and provides indication at a remote location of the protector’s
on-off status.
main protector contacts, and will open regardless of whether
the protector contacts are opened manually or electrically. For
auxiliary switch ratings below 6Vac or 5Vdc, an auxiliary
switch with gold contacts designated as REG is available. Gold
contacts are not recommended for load current above 100
milliamps.
Note:
A: Terminal protrusion dimensions are referenced from back mounting panel.
B: Main terminals are male push-on type .250 [6.35] wide x 0.31 [.79] thick x .375 [9.53] long or 8-32
Amp
Auxiliary switch contacts actuate simultaneously with the
x .187 [4.75] screw type. Metric screw terminals are M4 x 5mm (<=30A): M5 x 5mm screw type
(>30A). On VDE approved builds with screw terminals, external tooth lockwashers are supplied. On
VDE approved builds with push-on terminals a soldered connection is required above 25 amperes.
Push-On
X
Screw
8-32
X
Screw
M4
X
Screw
10-32
X
Screw
M5
X
IAG/IUG/IEG/CEG/LEG Series - Configurations
[ 38.86 ]
1.530
1.083
[ 27.51 ]
Optional flat
screw terminal
Standard Auxiliary Switch
.230
[ 5.84 ]
.110
[ 2.79 ]
Series with Auxiliary Switch
.848
[ 21.53 ]
OFF POSITION
BREAKER IN
NO
NC
C
–IREC4
–IREG4
.441
[ 11.20 ]
2.438 MAX.
[ 61.93 ]
(See Note A)
.260
[ 6.60 ]
Series
[ 35.05 ]
1.380
[ 5.84 ]
.230
[ 38.86 ]
1.530
1.059
[ 26.90 ]
[ 38.86 ]
VDE Auxiliary Switch
1.530
.187
[ 4.75 ]
.764
[ 19.04 ]
.
[ 5.84 ]
2.52 MAX.
[ 64.00 ]
(See Note A)
230
–IREC5
.469
[ 11.91 ]
2.454 MAX.
[ 62.33 ]
(See Note A)
.250
[ 6.35 ]
Switch
Only
Shunt
114

Related parts for IEGH66-1-62-20.0-21-V