2866475 Phoenix Contact, 2866475 Datasheet - Page 3

no-image

2866475

Manufacturer Part Number
2866475
Description
POWER SUPPLY 5A 12VDC
Manufacturer
Phoenix Contact
Series
Trior
Type
Industrialr
Datasheets

Specifications of 2866475

Voltage - Output
12V
Number Of Outputs
1
Power (watts)
60W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
12 VDC @ 5A
Size / Dimension
4.53" L x 1.26" W x 5.12" H (115mm x 32mm x 130mm)
Operating Temperature
-25°C ~ 70°C
Power (watts) - Rated
60W
Efficiency
83%
Approvals
cUL, EN, UL, VDE
Product
Switching
Commercial/medical
Commercial
Output Power Rating
60 W
Input Voltage
100 VAC to 240 VAC
Output Voltage (channel 1)
12 V
Output Current (channel 1)
5 A
Mounting Style
DIN Rail
Brand/series
TRIO
Configuration
Enclosed
Operation
Switching
Output
12 VDC @ 5 A
Phoenix Part Number
TRIO-PS/1AC/12DC/5
Power, Output
60 W
Primary Type
AC-DC
Voltage, Input
85 to 264 VAC
Voltage, Output
12 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
277-2146
TRIO-PS/1AC/12DC/5
TRIO-PS/ 1AC/12DC/ 5
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866475
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Maximum power dissipation idling
Power loss nominal load max.
General data
Width
Height
Depth
Net weight
Operating voltage display
Efficiency
Insulation voltage input/output
Degree of protection
Class of protection
MTBF
Ambient temperature (operation)
Ambient temperature (storage/transport)
Max. permissible relative humidity (operation)
Mounting position
Assembly instructions
Electromagnetic compatibility
Noise immunity
Low Voltage Directive
Standard – Electrical equipment of machines
Standard - Safety of transformers
Standard - Electrical safety
Standard – Electronic equipment for use in
electrical power installations and their assembly
into electrical power installations
Standard – Safety extra-low voltage
Standard - Safe isolation
Standard – Protection against electric shock
Order No.: 2866475
0.9 W
11 W
32 mm
130 mm
115 mm
0.5 kg
LED green
> 83 % (At 230 V AC and nominal values)
4 kV AC (type test)
2 kV AC (routine test)
IP20
I, with PE connection
> 500 000 h in acc. with IEC 61709 (SN 29500)
-25 °C ... 70 °C (> 55° C derating)
-40 °C ... 85 °C
95 % (at 25 °C, no condensation)
Horizontal DIN rail NS 35, EN 60715
Can be aligned: Horizontal 0 cm, vertical 5 cm
Conformance with EMC directive 2004/108/EC
EN 61000-6-2:2005
Conformance with LV directive 2006/95/EC
EN 60204
EN 61558-2-17
EN 60950/VDE 0805 (SELV)
EN 61558-2-17
EN 50178/VDE 0160 (PELV)
EN 60950 (SELV)
EN 60204 (PELV)
DIN VDE 0100-410
DIN VDE 0106-1010
DIN 57100-410
Oct 8, 2010