2866653 Phoenix Contact, 2866653 Datasheet
2866653
Specifications of 2866653
Related parts for 2866653
2866653 Summary of contents
Page 1
... Make sure you always use the the latest documentation. It can be downloaded at www.download.phoenixcontact.com. A conversion table is available on the Internet at www.download.phoenixcontact.com/general/7000_en_00.pdf. © PHOENIX CONTACT - 11/2006 Area of application The power supply unit complies with standard EN 60079-15 and may be installed within the potentially hazardous area in which category 3G electrical apparatus is necessary. ...
Page 2
... Peak switching voltages Connection in parallel Surge protection against internal surge voltages Resistance to reverse feed 103074_00_en MINI-PS-100-240AC/24DC/1.5/EX Type Order No. MINI-PS-100-240AC/24DC/1.5/EX 2866653 Type Order No. ME 17,5 TBUS 1,5/ 5-ST-3,81 GN 2709561 100 V AC ... 240 V AC (wide-range input ... 264 ... 65 Hz Approx. 0.75 A (120 V AC) Approx. 0.45 A (230 V AC) 2 < ...
Page 3
... IEC 61709 (SN 29500) Polyamide PA, color: green 0.25 kg -25 °C ... 70 °C (> 60°C derating) -40 °C ... 85 ° (at 25°C, no condensation) < 15 Hz, amplitude ±2 acc. with IEC 60068-2 ... 150 Hz, 2.3g, 90 min. 30g in all directions in acc. with IEC 60068-2-27 2 3K3 (in acc. with EN 60721) 3 PHOENIX CONTACT ...
Page 4
... Comments Criterion B Input/Output/Signal Level 3 - asymmetrical Frequency range 0.15 MHz ... 80 MHz Voltage 10 V Comments Criterion A Input (mains buffering > 20 ms) Comments Criterion B EN 55011 (EN 55022) Class B, area of application: Industry and residential EN 55011 (EN 55022) Class B, area of application: Industry and residential MINI-PS-100-240AC/24DC/1.5/EX PHOENIX CONTACT 4 ...
Page 5
... The power supply unit complies with stan- dard EN 60079-15 and may be installed within the potentially hazardous area in which category 3G electrical apparatus is necessary. 2 [mm ] AWG solid stranded 0.2 - 2.5 0 0.2 - 2.5 0 0.2 - 2.5 0 PHOENIX CONTACT [Nm] Torque 0.5 - 0.6 0.5 - 0.6 0.5 - 0.6 5 ...
Page 6
... In order to guarantee sufficient convection, we recommend observing the following minimum distance to other modules vertical di- rection and horizontal direction. The power supply unit can be snapped onto all DIN rails in acc. with EN 60715. They must be horizontal (connecting terminal blocks above and below). PHOENIX CONTACT 6 ...
Page 7
... Position the module with the DIN rail guide on the upper edge of the DIN rail, and snap it in with a downward motion. Dismantling Pull the snap lever open with the aid of a screwdriver and slide the module out at the lower edge of the DIN rail. MINI-PS-100-240AC/24DC/1.5/EX PHOENIX CONTACT 7 ...
Page 8
... If an internal fuse is triggered, there is most probably a malfunction in the device. In this case, the device must be inspected in the factory! The power supply unit cannot be repaired by the user and must be replaced by an equivalent. PHOENIX CONTACT ...
Page 9
... State 2 OFF Open 1. The output voltage is less than 21.5 V. There is a secondary consumer short circuit or overload. 2. There is no input voltage or there is a device fault. PHOENIX CONTACT 9 ...
Page 10
... For ambient temperatures above 60°C, the output current must be reduced by 2.5% per Kelvin increase in tempera- 60 ture. From 70°C onwards or in the case of thermal overload, the device reduces the output capacity for its own protection, and returns to normal operation when it has cooled down. MINI-PS-100-240AC/24DC/1.5/EX PHOENIX CONTACT 10 ...
Page 11
... N + − + − + PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany 103074_00_en Parallel operation Due to the current carrying capacity, a maximum of two de- vices may be connected in parallel on the DIN rail connector for redundancy. Without using the DIN rail connector, de- vices of the same type can be connected in parallel both for redundancy reasons as well as to improve performance ...