2967620 Phoenix Contact, 2967620 Datasheet - Page 2

no-image

2967620

Manufacturer Part Number
2967620
Description
General Purpose / Industrial Relays PLC-RSC-24DC/21HC RELAY PN 651-2961312
Manufacturer
Phoenix Contact
Series
-r
Datasheets

Specifications of 2967620

Contact Form
SPDT
Coil Voltage
24 V
Contact Rating
6 A at 250 V
Contact Termination
PCB
Mounting Style
PCB
Power Consumption
140 W
Contact Material
Silver Tin Oxide
Coil Current
15.3 mA
Brand/series
PLC-RSC/RSP
Current, Rating
10 A
Dimensions
80 mm L x 14 mm W x 94 mm H
Function
PLC
Material, Contact
AgNi
Phoenix Part Number
PLC-RSC-24DC/21HC
Power, Rating
240 W
Relay Type
Electro Mechanical
Standards
cULus, UL, RoHS
Termination
Screw
Voltage, Control
24 VDC
Voltage, Rating
250 VAC/VDC
Contact Rating (current)
10A
Switching Voltage
250VAC, 250VDC - Max
Coil Type
Non Latching
Turn On Voltage (max)
-
Turn Off Voltage (min)
-
Features
LED Indicator, PLC Terminal Block
Mounting Type
DIN Rail
Termination Style
Screw Terminal
Operate Time
8ms
Release Time
10ms
Coil Power
-
Coil Resistance
-
Operating Temperature
-40°C ~ 60°C
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
PLC-RSC- 24DC/21HC
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2967620
PHOENIX CONTACT GmbH & Co. KG
Typical release time
Operating voltage display
Name of protection
Protective circuit/component
Contact side
Contact type
Contact material
Maximum switching voltage
Minimum switching voltage
Maximum inrush current
Min. switching current
Limiting continuous current
Interrupting rating (ohmic load) max.
Interrupting rating (ohmic load) max. bridged
General data
Length
Height
Width
Test voltage relay winding/relay contact
Ambient temperature (operation)
Ambient temperature (storage/transport)
Operating mode
Service life mechanical
Inflammability class in acc. with UL 94 (housing)
Order No.: 2967620
10 ms
Yellow LED
Polarity protection
Polarity protection diode and TAZ diode
Single contact, 1-PDT
AgNi
250 V AC/DC (The separating plate PLC-ATP should be installed
for voltages larger than 250 V (L1, L2, L3) between identical
terminal blocks in adjacent modules. Potential bridging is then
carried out with FBST 8-PLC... or ...FBST 500...)
12 V AC/DC
30 A (300 ms)
100 mA
10 A
6 A (value applies to connections 12. If connections 12 are
bridged, the normal value applies.)
240 W (for 24 V DC)
58 W (for 48 V DC)
48 W (for 60 V DC)
50 W (for 110 V DC)
80 W (for 220 V DC)
2500 VA (for 250 V AC)
144 W (for 24 V DC. Value applies to connections 12. If
connections 12 are bridged, the normal value applies.)
1500 VA (for 250 V AC. Value applies to connections 12. If
connections 12 are bridged, the normal value applies.)
80 mm
94 mm
14 mm
4 kV AC (50 Hz, 1 min)
-25 °C ... 60 °C
-40 °C ... 85 °C
100% operating factor
3 x 10
V0
7
cycles
May 31, 2008