755XBXC-24A Magnecraft / Schneider Electric, 755XBXC-24A Datasheet - Page 2

General Purpose / Industrial Relays SINGLE COIL 24VAC

755XBXC-24A

Manufacturer Part Number
755XBXC-24A
Description
General Purpose / Industrial Relays SINGLE COIL 24VAC
Manufacturer
Magnecraft / Schneider Electric
Series
755Xr
Datasheets

Specifications of 755XBXC-24A

Coil Resistance
740 Ohms
Contact Form
DPDT
Coil Voltage
24 V
Contact Rating
10 A
Contact Material
Silver Cadmium Oxide
Relay Type
Latching
Coil Voltage Vac Nom
24V
Contact Current Max
16A
Contact Voltage Ac Nom
277V
Contact Voltage Dc Nom
28V
Contact Configuration
DPDT
Coil Type
AC
Current, Rating
16 A
Function
Latching
Latch Type
Magnetic
Mounting Type
Socket
Number Of Pins
11
Standards
UL, CSA, RoHS
Termination
Plug-In
Voltage, Control
24 VAC
Voltage, Rating
277 VAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Alternating Relay – Application Data
712 Alternating Relay
In many industrial pumping applications, two identical pumps are used for the same job. A standby unit is available in case
the first pump fails. However, a completely idle pump might deteriorate and provide no safety margin. Alternating relays
prevent this by assuring that both pumps get equal run time.
The Model 712 Series Alternating Relay is designed for duplex pumping systems where it is desirable to equalize pump run
time. The solid state alternating circuit drives an internal electromechanical relay. A continuous power source and control
switch is required.
The control switch (float, pressure or other isolated contact) is connected as shown in the respective wiring diagrams. Each
time the control switch is opened the output contacts will change status. Indicator lights on the case show the internal relay
status.
Setting the top toggle switch to the “center position” alternates the load; while setting the switch to “Load 1” or “Load 2” will
lock the relay in the respected position, preventing alternation.
The alternating relay approach isn’t limited to pumping applications. The control switches could be thermostats or pressure
switches, and the loads could be fans or compressors.
Applications:
INDUSTRIAL
INDUSTRIAL
PACKING
PUMPING
INDUSTRIAL
COMPRESSORS
AUTOMATION
APPLIANCES
MACHINES
MACHINES
FANS
www.magnecraft.com
847-441-2540
7/3
M ag n e cr a f t S olu t i o n G ui de 10 5A