US-08 Omron, US-08 Datasheet
US-08
Specifications of US-08
Related parts for US-08
US-08 Summary of contents
Page 1
... Four time ranges are selectable per timer unit. • Wide timing range of 0.05 second to 30 hours can be covered by a combination of five timer units. • Standard surface mounting type is easily convertible to flush mounting type with the use of a special adapter (Y92F-40). • Requires only for mounting space. ...
Page 2
... Note: 1. Color indicators for the rated voltage are provided on the front of the Timer. Blue: 100/110/120 VAC Red: 200/220/240 VAC None: Other voltages 2. With DC ratings, single-phase full-wave rectified power sources may be used. 3. 90% to 110% for 12-VDC models. ■ Characteristics ±1% max. (see note) Accuracy of operating time ± ...
Page 3
Engineering Data Load current (A) Operation ■ Timing Chart H3M Rt Set time Set time 7-2 (Power) 1-4 (NC) 1-3 (NO) 8-5 (NC) 8-6 (NO) Power ON indicator lamp Time-out indicator Rt: Resetting time Reference: A maximum current of 0.15 ...
Page 4
... Note: When two or more timers mounted in line are to be continuously energized at the same time after the lapse of the set time, be sure to limit the carry current to less than 1 A. When using the timers at an ambient temperature of more than 40°C, be sure to reset the timers immediately after the set time has elapsed. ...
Page 5
Back Connecting Socket PL08 Two, 2 dia. holes P3G-08 Mounting Track PFP-100N/PFP-50N (See note) Note: This dimension applies to PFP-50N. Terminal Arrangement Mounting Holes (Bottom View) Two, 3.5 dia socket mounting holes Terminal Arrangement (Bottom View) End Plate ...
Page 6
... Other Precautions • power supply must have 50% or less ripple and the average voltage must be within the rated supply voltage specification. • A P3G-08 Socket can be used instead of a US-08 Socket to reduce the depth. Also, the P3G-08 has screw terminals, making maintenance easier. ...
Page 7
... PERFORMANCE DATA Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability ...