HRPG-450-48 Mean Well, HRPG-450-48 Datasheet - Page 3

Linear & Switching Power Supplies 456W 48V 9.5A W/PFC EISA Compliant

HRPG-450-48

Manufacturer Part Number
HRPG-450-48
Description
Linear & Switching Power Supplies 456W 48V 9.5A W/PFC EISA Compliant
Manufacturer
Mean Well
Datasheet

Specifications of HRPG-450-48

Product
Switching
Commercial/medical
Commercial
Output Power Rating
456 W
Input Voltage
85 VAC to 264 VAC, 120 VDC to 370 VDC
Number Of Outputs
1
Output Voltage (channel 1)
48 V
Output Current (channel 1)
9.5 A
Mounting Style
Chassis
Dimensions
218 mm L x 105 mm W x 41 mm H
Open Frame/enclosed
Enclosed
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Function Description of CN100
Function Manual
1.Remote Sense
2.DC-OK Signal
3.Remote Control
The remote sensing compensates voltage drop on
the load wiring up to 0.5V.
DC-OK signal is a TTL level signal. High when PSU turns on.
The PSU can be turned ON/OFF by using the
"Remote Control" function.
Pin No. Function Description
Between DC-OK(pin5) and GND(pin6)
3.3 ~ 5.6V
0 ~ 1V
Between RC+(pin1) and RC-(pin2)
SW ON (Short)
SW OFF (Open)
1
2
3
4
5
6
7
8
DC-OK DC-OK Signal is a TTL level signal, referenced to pin6(DC-OK GND). High when PSU turns on.
AUXG
GND
RC+
AUX
RC-
+S
-S
450W Single Output with PFC Function
Turns the output on and off by electrical or dry contact between pin 2 (RC-), Short: Power OFF, Open: Power ON.
Remote control ground.
Auxiliary voltage output, 4.75~5.25V, referenced to pin 4(AUXG). The maximum load current is 0.3A. This output has the built-in oring
diodes and is not controlled by the "remote ON/OFF control".
Auxiliary voltage output ground. The signal return is isolated from the output terminals (+V & -V).
This pin connects to the negative terminal(-V). Return for DC-OK signal output.
Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be twisted in pair to
minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be twisted in pair to
minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
Output Status
Output Status
OFF
OFF
ON
ON
2
2
2
8
8
8
CN100
CN100
CN100
1
7
1
7
1
7
(Pin7)
+S
Fig 1.1
Fig 2.1
Fig 3.1
+
LOAD
-
H R P G - 4 5 0
(Pin8)
-S
Sense lines should
be twisted in pairs
File Name:HRPG-450-SPEC 2010-11-29
SW
2
8
2
8
2
8
AUXG
AUXG
AUXG
GND
GND
GND
RC-
RC-
RC-
-S
-S
-S
CN100
CN100
CN100
s e r i e s
DC-OK
DC-OK
DC-OK
RC+
AUX
RC+
AUX
RC+
AUX
+S
+S
+S
1
7
1
7
1
7

Related parts for HRPG-450-48