SDP2-24-100T SOLA HEVI DUTY, SDP2-24-100T Datasheet - Page 2

Linear & Switching Power Supplies 24-28V 2.1A Output

SDP2-24-100T

Manufacturer Part Number
SDP2-24-100T
Description
Linear & Switching Power Supplies 24-28V 2.1A Output
Manufacturer
SOLA HEVI DUTY
Type
Industrialr
Datasheets

Specifications of SDP2-24-100T

Product
Switching
Output Power Rating
50 W
Number Of Outputs
1
Output Voltage (channel 1)
24 V
Output Current (channel 1)
2.1 A
Dimensions
91 mm L x 45 mm W x 75 mm H
Power Supply Type
Switching
Power Supply Output Type
Fixed
No. Of Outputs
1
Output Voltage
24V
Output Current
2.1A
Power Rating
50.4W
Input Voltage
85V AC To 264V AC / 90V DC To 375V DC
Brand/series
SDP Series
Configuration
Enclosed
Current, Rating
1.1⁄0.7 A
Frequency
47 to 63 Hz
Height
2.95 in.
Mounting Type
DIN Rail
Operation
Switching
Output
24 to 28 VDC @ 2.1 A
Power, Output
100 W
Primary Type
AC-DC
Temperature, Operating, Maximum
60 °C
Temperature, Operating, Minimum
-10 °C
Voltage, Input
85 to 264/90 to 375 VAC/VDC
Voltage, Output
24 to 28 VDC
Voltage, Rating
85 to 264 VAC⁄90 to 375 VDC
Width
1.77 in.
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
SDP™ Series Specifications (24 V models)
Notes:
1. Not UL listed for DC input.
2. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth scope and 50 Ohm resistor.
3. For all models except SDP 4-24-100LT.
Input Voltage
Input Frequency
Input Current
External Fusing
Hold-Up Time
Efficiency
Losses
Output Voltage
Voltage Regulation
Ripple/Noise
Overvoltage Protection (OVP)
Output Noise
Suppression
Rated Continuous
Loading
Overload Behavior
Protection
Power Back Immunity
Status Indicators
Case & Mounting
(H x W x D) (in/mm)
Weight - lbs (kg)
Mounting Orientation
Ventilation/Cooling
Connection
Temperature
MTBF
Humidity
Electromagnetic
Emissions (EME)
Electromagnetic
Immunity (EMI)
Safe Low Voltage
Protection Class/Voltage
Warranty
CB Scheme, EN60950, UL60079-15 (Class 1, Zone 2 Hazardous Locations, Temp Class T3), UL508 Listed, cULus, UL 60950, cURus, CE (LVD 73/23 & 93/68/EEC). (EMC
89/336 & 93/68/EEC). EN61000-3-2, NEC Class 2 power supply acc. To NFPA 70 art. 725-41 (a)(2).
•Free space for cooling
•Connector size range
Description
2
1
SDP 06-24-100T
0.63 A @ 24 Vdc /
(75 x 22.8 x 96.7)
0.54 A @ 28 Vdc
0.35 lbs (.16 kg)
2.95 x 0.9 x 3.8
0.4 A / 0.25 A
< 3.75 W typ.
> 80% typ.
Storage: -25°C...+85°C Operation: -10°...+60°C full power with linear derating to half power from 60°C to 70°C.
contact Technical Services at (800) 377-4384 with any questions.
Input: screw terminals, connector size range: 20-12AWG (1.5 - 6 mm
> 30 Vdc, but < 33 Vdc, auto recovery
EN61000-6-2 (Includes EN61000-6-1) (EN55024) Criterion A: no derogation of performance
Continuous operation at overload/short-circuit: up to 1.5 x Nominal Current Continuous
24 V (22.5 - 28.5 Vdc Adj.)
85-264 Vac, 90-375 Vdc
Molded plastic housing using UL 94 approved flameproof material rating 94V-2.
Visit our website at www.solahd.com or
Unit is continuously protected against short-circuit, overload and open-circuit.
Standard: Vertical; Optional: Horizontal or on top (Contact Technical Services).
SDP 1-24-100T
1.3 A @ 24 Vdc /
> 500,000 hours according to Telcordia/Bellcore Document SR-332, Issue 1.
1.1 A @ 28 Vdc
Normal convection, no fan required; Above/below: 25 mm recommended.
0.7 A / 0.4 A
EN61000-6-3 (Includes EN61000-6-4) Class B (EN 55022) incl. Annex A
< 6.1 W typ.
> 83% typ.
2.95 x 1.77 x 3.58 (75 x 45 x 91)
Not required. Unit provides internal fuse (T3A, not accessible)
Simple snap-on to DIN TS35/7.5 or TS35/15 rail system.
Up to 90% RH, noncondensing; IEC 68-2-2, 68-2-3
0.5 lbs (.23 kg)
(Convection cooling, no forced air required).
IP20 (IEC529), Protection Class 1 (IEC536)
Static 0.5% V
Dimensions
Radiated EMI values below EN61000-6-2
Installation
General
Output
Safety
Input
Power Supplies
Green LED on, when V
SELV (acc. EN60950)
SDP 2-24-100T
2.1 A @ 24 Vdc /
Catalog Number
1.8 A @ 28 Vdc
out
1.1 A / 0.7 A
< 8.1 W typ.
> 86% typ.
, dynamic + 2% V
< 50 mVpp
47-63 Hz
> 25 ms
3 years
3
35 V
out
“OK”.
out
overall\
24 V (24 - 25.7 Vdc Adj.)
2
) for solid or stranded conductors.
> 26 Vdc, but < 27.2
Vdc, auto recovery
SDP 4-24-100LT
3.8 A @ 24.5 Vdc
1.8 A / 1.0 A
85-132 / 176-264 Vac, 210-375 Vdc
(75 x 72.5 x 96.7)
2.95 x 2.85 x 3.8
0.7 lbs (.32 kg)
< 12 W typ.
> 88% typ.
24 V (22.5 - 28.5 Vdc Adj.)
> 30 Vdc, but < 33 Vdc,
4.2 A @ 24.5 Vdc /
SDP 4-24-100RT
3.6 A @ 28 Vdc
auto recovery
2.2 A / 1.2 A
4
119

Related parts for SDP2-24-100T