HLG-240-30A Mean Well, HLG-240-30A Datasheet
HLG-240-30A
Specifications of HLG-240-30A
Related parts for HLG-240-30A
HLG-240-30A Summary of contents
Page 1
... ENVIRONMENT TEMP. COEFFICIENT 0.03%/ VIBRATION 10 ~ 500Hz, 5G 12min./1cycle, period for 72min. each along axes SAFETY STANDARDS UL1012, TUV EN61347-1, EN61347-2-13 independent (except for HLG-240H C type), UL60950-1, UL8750, TUV EN60950-1, IP65 or IP67 approved Note.7 WITHSTAND VOLTAGE I/P-O/P:3.75KVAC SAFETY & ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH ...
Page 2
... IP65 rated. Output voltage and constant current level can be adjusted through internal potential meter. (Can access by removing the rubber stopper on the case.) 244.2 220.2 12 9.6 244.2 220 Case No.954C 300 20 SJTW 14AWG 2C 4.2 4PL 300 ADJ. ADJ. SJTW 14AWG 2C 4.2 4PL File Name:HLG-240-SPEC 2011-01- Unit:mm +V(Red) -V(Black) +V(Red) -V(Black) ...
Page 3
... Open Open 820 1.8K 680 620 820 120 500 82 68 150 Short Short Short Short Short AC Input Terminal Pin No. Assignment 1 Pin No. O ADJ 4.2 4PL DC Output Terminal Pin No. Assignment Pin No File Name:HLG-240-SPEC 2011-01- +V(Red) -V(Black) ADJ1(Blue) ADJ2(White) Assignment FG AC/L AC/N Assignment -V +V ...
Page 4
... Power Factor Characteristic Power factor will be higher than 0.9 when output loading is 65% or higher. Constant Current Mode LOAD EFFICIENCY vs LOAD (48V Model) HLG-240 series possess superior working efficiency that up to 94% can be reached in field applications 10% 20% 30% 40% 50% LOAD POWER SWITCHING O.L.P. PWM & PFC ...
Page 5
... LED driver circuit should use 2.2uF ~ 22uF(typ.) of rating depends on the operating frequency of the LED driver. The higher the operating frequency is used, the smaller value of Cin should be chosen, and vice versa. AC I/P HLG-240 source (B) Constant Current area (C) Hiccup Io (%) O/P O/P R Cin Cout L IC Circuit File Name:HLG-240-SPEC 2011-01- ...
Page 6
... A. Add a common mode ferrite choke on output wires to reduce the common emission between 10M ~ 300MHz per lighting EMI regulation. B. Chassis of LED lamp and chassis of HLG-240 or the FG wire should be connected to the safety ground to reduce the EMI noise, including the conduction and radiation emission. ...