NFS40-7915J Emerson Network Power, NFS40-7915J Datasheet

Linear & Switching Power Supplies 15v 40W 3 x 5 Medical

NFS40-7915J

Manufacturer Part Number
NFS40-7915J
Description
Linear & Switching Power Supplies 15v 40W 3 x 5 Medical
Manufacturer
Emerson Network Power
Series
NFS40r
Datasheet

Specifications of NFS40-7915J

Product
Switching
Commercial/medical
Medical
Output Power Rating
40 W
Input Voltage
85 VAC to 264 VAC, 120 VDC to 370 VDC
Number Of Outputs
1
Output Voltage (channel 1)
15 V
Output Current (channel 1)
2.6 A
Mounting Style
Chassis
Dimensions
5 in L x 3 in W x 1.2 in H
Open Frame/enclosed
Open Frame
Lead Free Status / RoHS Status
Lead free / RoHS Compliant

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
NFS40-7915J
Manufacturer:
ARTESYN
Quantity:
1 000
NFS40 Medical Series
Single & Triple Output
Special Features
• 5.0 x 3.0 x 1.2 inch package
• Industry standard package
• Overvoltage and short circuit
• 40 W with free air convection
• EN55022, EN55011 conducted
• UL, VDE and CSA safety approvals
• Available RoHS compliant
• 2 year warranty
Safety
Total Power:
Input Voltage: 85 - 264 VAC
# of Outputs:
(1U applications)
UL2601
CSA22.2 No. 125
IEC601/VDE0750
protection
noise level A
40 - 50W
120 - 370 VDC
Single, triple
Electrical Specifications
Output
Input
Input voltage range:
Input frequency range:
Input surge current:
Safety ground leakage
current:
Voltage adjustability:
Line regulation:
LL to HL, FL
Load regulation:
FL to NL
Transient response:
Temperature coefficient:
Overvoltage protection:
Output power limit:
Short circuit protection:
+5 V output on triples
Vout on singles
Main output
Auxiliary outputs
Main output
Auxiliary outputs
+5 V (1.5 - 3 A step)
All outputs
+5 V output
Primary power limited
Single outputs
Multiple outputs
110 Vac, 60 Hz, cold start
230 Vac, 50 Hz, cold start
110 Vac, 60 Hz
230 Vac, 50 Hz
Embedded Power for
Business-Critical Continuity
± 5.0%
± 5.0%
± 0.2%
± 1.0%
± 2.0%
± 5.0%
± 120 mV max. dev.
500 µs recovery
±0.02%/°C
6.25 ± 0.75 Vout
90 W input power limit
Continuous
Short term
85 - 264 Vac
120 - 370 Vdc
47 - 440 Hz
10 A
22 A
18 µA max.
28 µA max.
Rev.06.9.09_118
NFS40 Medical
1 of 4

Related parts for NFS40-7915J

NFS40-7915J Summary of contents

Page 1

... NFS40 Medical Series Single & Triple Output Total Power 50W Input Voltage 264 VAC 120 - 370 VDC # of Outputs: Single, triple Special Features • 5.0 x 3.0 x 1.2 inch package (1U applications) • Industry standard package • Overvoltage and short circuit protection • with free air convection • ...

Page 2

... Vac 1500 Vac 20 - 110 kHz 270 g (9.6 oz) 170,000 hours 0° +70 °C -40 °C to +85 ° CFM Derate linearly to 50% load 95% RH 10,000 feet max. 40,000 feet max. 0.75 G peak Embedded Power for Business-Critical Continuity Rev.06.9.09_118 NFS40 Medical  of 4 ...

Page 3

... Regulation (5) ± 2.0% NFS40-7908J ± 5.0% ± 5.0% ± 2.0% NFS40-7910J ± 10%/-3.0% ± 5.0% ± 2.0% NFS40-7912J ± 2.0% NFS40-7915J ± 2.0% NFS40-7924J ± 2.0% NFS40-7928J ± 5.0% ± 5.0% Pin Connections -7908J, -7928J -7910J SINGLES AC Line AC Line AC Line ...

Page 4

... P1. Use metal stand-offs attached to a common metal chassis. This connection also significantly attenuates common mode noise standard L-bracket and enclosure kit is available for mounting which contains all screws, connectors and necessary mounting hardware. Order part number NFS40CJ. 5.00 (127.00) ...