DR-120-48 Mean Well, DR-120-48 Datasheet

Linear & Switching Power Supplies 120W 48V 2.5A

DR-120-48

Manufacturer Part Number
DR-120-48
Description
Linear & Switching Power Supplies 120W 48V 2.5A
Manufacturer
Mean Well
Datasheets

Specifications of DR-120-48

Product
Switching
Commercial/medical
Commercial
Output Power Rating
120 W
Input Voltage
88 VAC to 132 VAC, 248 VDC to 370 VDC
Number Of Outputs
1
Output Voltage (channel 1)
48 V
Output Current (channel 1)
2.5 A
Mounting Style
DIN Rail
Output Type
DC
Power Supply Type
Switch Mode
Power Supply Output Type
Fixed
No. Of Outputs
1
Input Frequency
63Hz
Output Voltage
48V
Output Current
2.5A
Power Rating
120W
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
SPECIFICATION
MODEL
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY &
EMC
(Note 4)
OTHERS
NOTE
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
OVER VOLTAGE
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
HARMONIC CURRENT
EMS IMMUNITY
MTBF
DIMENSION
PACKING
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.)
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
EMI CONDUCTION & RADIATION
120W Single Output Industrial DIN RAIL Power Supply
Note.3
Note.2
DR-120-12
12V
10A
0 ~ 10A
120W
80mVp-p
12 ~ 14V
500ms, 70ms
36ms
88 ~ 132VAC/176 ~ 264VAC by switch
47 ~ 63Hz
85
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
105 ~ 150% rated output power
15 ~ 16.5V
Protection type : Shut down o/p voltage, re-power on to recover
-10 ~ +60
20 ~ 90% RH non-condensing
-20 ~ +85 , 10 ~ 95% RH
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508,
I/P-O/P:3KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
Compliance to EN55011,EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
136.8Khrs min.
65.5*125.2*100mm (W*H*D)
0.79Kg; 20pcs/16.5Kg/1.29CUFT
80%
2.6A/115VAC
COLD START 20A/115VAC
<3.5mA / 240VAC
Protection type : Constant current limiting, recovers automatically after fault condition is removed
2.0%
0.5%
1.0%
0.03%/
/230VAC
5
UL60950-1,
(TSW1)
(0 ~ 50
(Refer to output load derating curve)
/230VAC
I/P-FG:1.5KVAC
MIL-HDBK-217F (25 )
1.6A/230VAC
32ms
TUV EN60950-1 approved
/115VAC at full load
500ms, 70ms
40A/230VAC
O/P-FG:0.5KVAC
/115VAC at full load
DR-120-24
248 ~ 370VDC
24V
5A
0 ~ 5A
120W
80mVp-p
24 ~ 28V
84%
29 ~ 33V
90
1.0%
0.5%
1.0%
5 (TSW1)
D R - 1 2 0
DR-120-48
48V
2.5A
0 ~ 2.5A
120W
100mVp-p
48 ~ 53V
85%
58 ~ 65V
90
1.0%
0.5%
1.0%
5 (TSW1)
File Name:DR-120-SPEC 2008-04-07
s e r i e s

Related parts for DR-120-48

DR-120-48 Summary of contents

Page 1

... UL60950-1, TUV EN60950-1 approved I/P-FG:1.5KVAC O/P-FG:0.5KVAC MIL-HDBK-217F ( DR-120-48 48V 2. 2.5A 120W 100mVp 53V 1.0% 0.5% 1.0% 85 65V 5 (TSW1 (TSW1) File Name:DR-120-SPEC 2008-04- ...

Page 2

... RECTIFIERS & FILTER DETECTION CIRCUIT O.V. 100 105 110 115 120 160 170 180 190 200 210 220 230 240 INPUT VOLTAGE (V) 60Hz File Name:DR-120-SPEC 2008-04- Unit:mm fosc : 55KHz +V -V Ta=25 350 300 250 200 150 100 80 125 130 250 260 ...

Related keywords