SDN40-24-480 SOLA HEVI DUTY, SDN40-24-480 Datasheet - Page 3

no-image

SDN40-24-480

Manufacturer Part Number
SDN40-24-480
Description
Linear & Switching Power Supplies 3PH 24-28VDC 40A
Manufacturer
SOLA HEVI DUTY
Type
Industrialr
Datasheet

Specifications of SDN40-24-480

Product
Switching
Output Power Rating
960 W
Output Voltage (channel 1)
24 V
Output Current (channel 1)
40 A
Dimensions
282 mm L x 116 mm W x 124 mm H
Power Supply Type
Switching
Power Supply Output Type
Fixed
No. Of Outputs
1
Output Voltage
24V
Output Current
40A
Power Rating
960W
Input Voltage
340V AC To 576V AC / 450V DC To 820V DC
Brand/series
SDN Series
Configuration
Enclosed
Current, Rating
3.0 A (Nom.)
Frequency
47 to 63 Hz
Height
4.88 in.
Mounting Type
DIN Rail/Panel
Number Of Outputs
1
Operation
Switching
Output
24 VDC @ 40 A
Power, Output
960 W
Primary Type
AC-DC
Special Features
Parallelable, PFC
Temperature, Operating, Maximum
60 °C
Temperature, Operating, Minimum
-10 °C
Voltage, Input
340 to 576/450 to 820 VAC/VDC
Voltage, Output
24 VDC
Voltage, Rating
380 to 480 VAC
Width
11.1 in.
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
SDN
1. For the SDN 20-24-480C, single phase input is permissible, but output is derated
2. Not UL listed for DC input.
3. Input current ratings are conservatively specified with low input, worst case
H x W x D
(inches/mm)
Weight (lbs/kg)
Nominal Voltage
-AC Range
-DC Range
-Frequency
Nominal Current
-Inrush current max.
Efficiency (Losses
Power Factor
Correction
Nominal Voltage
-Tolerance
-Ripple
Overvoltage
Protection
Nominal Current
-Peak Current
-Current Limit
Holdup Time
Parallel Operation
EMC:
-Emissions
Approvals
Temperature
MTBF:
- Standard
Warranty
General Protection/
Safety
Status Indicators
Fusing
-Input
-Output
Mounting
Connections
Case
-Free Space
-Immunity
efficiency and power factor.
to 75% (15 Amps @ 24 Vdc).
TM
Description
5
Specifications (Three Phase)
2
7
6
3
4
)
EN61000-6-3, -4; Class B EN55011, EN55022 Radiated and Conducted including Annex A.
EN61000-6-1, -2; EN61000-4-2 Level 4, EN61000-4-3 Level 3; EN61000-4-6 Level 3; EN61000-4-4
Level 4 input and Level 3 output; EN61000-4-5 Isolation Class 4, EN61000-4-11;
CB Scheme, EN60950; UL508 Listed, cULus; UL60950, cRUus, CE (LVD 73/23 & 93/68/EEC). EN61000-3-2, UL60079-15
Class 1, Zone 2 Hazardous Location, Groups IIA, IIB, IIC w/T3 temp class up to 60°C Ambient.
Storage: -25°C...+85°C Operation. -10°C -60°C full power with operation to 70°C possible with a linear derating to half power from 60°C to 70°C
(Convection cooling, no forced air required). Operation up to 50% load permissible with sideways or front side up mounting orientation. The relative
humidity is < 90% RH, noncondensing; IEC 68-2-2, 68-2-3.
Protected against continuous short-circuit, overload, open-circuit. Protection Class 1 (IEC536), degree of protection IP20 (IEC 60529) Safe low voltage:
SELV (acc. EN60950)
Green LED on when V
2x Nominal Current < 2 sec.
5A through 30A units may be passively paralleled by selecting the “P” position of the switch on the unit. The SDN 40 contains active current balancing.
Input: IP20-rated screw terminals, connector size range: 16-10 AWG (1.5-6 mm
Outputs are capable of providing high currents for short periods of time for inductive load startup or switching. Fusing may be required for wire/loads
> 1,110,000 hours
> 90% typ. (12 W)
25 mm above and below, 25 mm left and right,
4.88 x 2.91 x 4.55
SDN 5-24-480
(124 x 73 x 116)
1.7 lbs (.77 kg)
5 A (120 W)
Simple snap-on system for DIN Rail TS35/7.5 or TS35/15 or chassis-mounted (optional screw mounting set SDN-PMBRK2 required).
0.5 A
6A,
1Ø or 3Ø 380-480 Vac
if 2x Nominal O/P current rating cannot be tolerated. Continuous current overload allows for reliable fuse tripping.
Fold Forward (Current rises, voltage drops to maintain constant power during overload up to max peak current)
out
15 mm in front
Output: Two connectors per output, connector size range: 16-10 AWG (1.5-6 mm
= 18V or greater.
> 40 ms
2x Nominal Current < 2 sec.
SDN 10-24-480
< ±2% overall (combination Line, load, time and temperature related changes)
> 940,000 hours
Fully enclosed metal housing with fine ventilation grid to keep out small parts.
4.88 x 3.5 x 4.55
2.16 lbs (.98 kg)
(124 x 89 x 116)
10 A (240 W)
typ. < 18 A
0.8 A
12A,
> 90% typ. (48 W)
> 30 Vdc, but < 33 Vdc, auto recovery
Installation
General
Output
Input
24 Vdc (22.5 - 28.5 Vdc adj.)
Power Supplies
2x Nominal Current < 2 sec.
Units Fulfill EN61000-3-2
MIL STD 217F @ 30
4. Losses are heat dissipation in watts at full load, nominal input line.
5. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth
6. Full load, 100 Vac Input @ T
7. For the SDN 40-24-480, output: one (+) two (-) connectors, size range 16-5 AWG
SDN 20-24-480C
Catalog Number
> 550,000 hours
(124 x 150 x 116)
3.97 lbs (1.8 kg)
4.88 x 5.9 x 4.55
380 - 480 Vac
Internally fused
450 - 820 Vdc
340 - 576 Vac
20 A (480 W)
scope and 50 Ohm resistor.
(1.5016 mm
< 50 mVpp
47 - 63 Hz
1Ø or 3Ø
> 28 ms
5 years
1.5 A
25A,
70 mm above and below, 25 mm left and right , 15 mm in front
2
) for solid conductors. 16-12 AWG (0.5-4 mm
2
) solid conductor.
1
o
C
35A, 2x Nominal Current
amb
> 90% typ. (72 W)
SDN 30-24-480
> 620,000 hours
4.88 x 9.72 x 4.55
(124 x 247 x 116)
4 lbs (1.81 kg)
= +25°C
30 A (720 W)
< 2 sec.
2.0 A
2
) for solid conductors.
3Ø 380 - 480 Vac
typ. < 30 A
> 20 ms
45A, 2x Nominal Current
2
) for flexible conductors.
> 90% typ. (96 W)
SDN 40-24-480
4.88 x 11.1 x 4.55
> 490,000 hours
(124 x 282 x 116)
6.6 lbs (2.99 kg)
40 A (960 W)
< 2 sec
3.0 A
4
109

Related parts for SDN40-24-480