DRT-240-48 Mean Well, DRT-240-48 Datasheet

Linear & Switching Power Supplies 240W 48V 5A

DRT-240-48

Manufacturer Part Number
DRT-240-48
Description
Linear & Switching Power Supplies 240W 48V 5A
Manufacturer
Mean Well
Datasheet

Specifications of DRT-240-48

Product
Switching
Commercial/medical
Commercial
Output Power Rating
240 W
Input Voltage
340 VAC to 550 VAC, 480 VDC to 780 VDC
Number Of Outputs
1
Output Voltage (channel 1)
48 V
Output Current (channel 1)
5 A
Mounting Style
DIN Rail
Output Type
DC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
SPECIFICATION
MODEL
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY &
EMC
(Note 4)
OTHERS
NOTE
AC CURRENT
INRUSH CURRENT (max.)
LEAKAGE CURRENT
OVERLOAD
OVER VOLTAGE
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMS IMMUNITY
MTBF
DIMENSION
PACKING
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.)
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
LINE REGULATION
LOAD REGULATION
SETUP, RISE, HOLD UP TIME
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
EMI CONDUCTION & RADIATION
240W Three Phase Industrial DIN RAIL Power Supply
Note.5
Note.3
Note.2
DRT-240-24
24V
10A
0 ~ 10A
240W
80mVp-p
24 ~ 28V
1200ms, 40ms, 20ms/400VAC
Three-Phase 340 ~ 550VAC (Dual phase operation possible)
47 ~ 63Hz
100
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
105 ~ 150% rated output power
30 ~ 36V
Protection type : Shut down o/p voltage, re-power on to recover
-20 ~ +70
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55011 (CISPR11), EN55022 (CISPR22), EN61204-3 Class B
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN61204-3, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
114.6Khrs min.
125.5*125.2*100mm (W*H*D)
1.3Kg; 12pcs/16.6Kg/1.29CUFT
89%
0.95A/400VAC
COLD START 50A
<3.5mA / 530VAC
Protection type : Constant current limiting, recovers automatically after fault condition is removed
1.0%
0.5%
0.5%
0.03%/
5
(0 ~ 50
(TSW) detect on heatsink of power switch
(Refer to output load derating curve)
I/P-FG:1.5KVAC
MIL-HDBK-217F (25 )
0.75A/500VAC
800ms, 40ms, 40ms/500VAC at full load
O/P-FG:0.5KVAC
DRT-240-48
48V
5A
0 ~ 5A
240W
80mVp-p
48 ~ 55V
59 ~ 66V
480 ~ 780VDC
1.0%
0.5%
0.5%
D R T- 2 4 0
File Name:DRT-240-SPEC 2008-11-25
s e r i e s

Related parts for DRT-240-48

DRT-240-48 Summary of contents

Page 1

... PACKING NOTE 1.0% 0.5% 0.5% 800ms, 40ms, 40ms/500VAC at full load 0.75A/500VAC 5 (TSW) detect on heatsink of power switch (Refer to output load derating curve) 0.03 I/P-FG:1.5KVAC O/P-FG:0.5KVAC MIL-HDBK-217F ( DRT-240-48 48V 240W 80mVp 55V 1.0% 0.5% 0.5% 480 ~ 780VDC 59 ~ 66V File Name:DRT-240-SPEC 2008-11- ...

Page 2

... AC/L2 4 AC/L1 Terminal Pin No. Assignment (TB2) Pin No. Assignment 1,2 DC OUTPUT +V 3,4 DC OUTPUT -V fosc : 70KHz RECTIFIERS & FILTER DETECTION CIRCUIT CURRENT LIMIT O.V.P. 370 385 400 415 430 460 475 490 505 520 550 INPUT VOLTAGE (VAC) 60Hz File Name:DRT-240-SPEC 2008-11- Unit: ...