N-48X Triad Magnetics, N-48X Datasheet

no-image

N-48X

Manufacturer Part Number
N-48X
Description
Transformers 115/115V 15VA XFMR ISOLATION XFMR
Manufacturer
Triad Magnetics
Type
Transformers and Autotransformersr
Datasheets

Specifications of N-48X

Power Rating
15 VA
Dimensions
84.15 mm W x 49.22 mm H
Product
Auto/Isolation Transformers
Height
49.22 mm
Width
84.15 mm
Brand/series
N Series
Capacity
15 VA
Configuration
Bobbin
Current, Secondary
0.13 A
Frequency
50/60 Hz
Hipot Rating
1500 V (RMS)
Length, Lead
7 "
Mounting Hole Centers
2.812 "
Mounting Type
Panel/Chassis
Number Of Outlets
1
Phase
1
Power, Rating
15 VA
Standards
UL Listed
Termination
Leadwires
Voltage, Primary
115 VAC
Voltage, Rating
115 VAC (Primary), 115 VAC (Secondary)
Voltage, Secondary
115 VAC
Weight
1.35 lbs.
Primary Voltages
115V
Secondary Voltages
115 VAC
Current Rating
130mA
Transformer Mounting
Chassis
Secondary Current Nom
0.13A
No. Of Phases
Single
Peak Reflow Compatible (260 C)
Yes
Rohs Compliant
Yes
Input Voltage
115VAC
Leaded Process Compatible
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
N-48X
Electrical Specifications (@25°C)
1. Maximum Power:
2. Input Voltage:
3. Output Voltage:
4. Full Secondary Load: 0.13 Amps RMS
5. Voltage Regulation: 20 % TYP @ full load to no load
Description:
The N-48X is power transformer for isolating equipment from direct connection to the
power line. It is constructed with nonconcentrically wound coils. The primary and
secondary are wound on separate arbors, then assembled on a laminate core
side-by-side separated by insulation. This prevents electrical connection under
normal or overload conditions between the primary and secondary windings.
Safety:
These units are designed with 1500V isolation between winding to winding and
between winding and core. Materials and construction are rated for Class B
insulation system.
Dimensions:
Weight: 1.35 lbs
Connections: 7.0±1” leads, 0.250±0.062” Skin & Tin
Schematic:
Input: Blk to Blk
Output: Red to Red
Shield: Wht
RoHS Compliance:
products meet the requirements of 2002/95/EC, known as the RoHS initiative.
1.937
A
3.312
B
As of manufacturing date February 2005, all standard
Unit: In inches
2.00
C
15 VA
115 V, 50 / 60 Hz
115V + 5%
2.812
D
BLK
BLK
WHT
RED
RED
P
C
HASSIS
O W E R
M
T
OUNT :
R A N S F O R M E R
Isolation
B
D
A
C

Related parts for N-48X

N-48X Summary of contents

Page 1

... Full Secondary Load: 0.13 Amps RMS 5. Voltage Regulation TYP @ full load to no load Description: The N-48X is power transformer for isolating equipment from direct connection to the power line constructed with nonconcentrically wound coils. The primary and secondary are wound on separate arbors, then assembled on a laminate core side-by-side separated by insulation ...

Page 2

... The primary and secondary are wound on separate arbors, then assembled on a laminate core side-by-side separated by insulation. This prevents : : Type Primary Volts Section No. VA Voltage ±5% A N-48X 15 115 115.0 B N-51X 35 115 115.0 C N-68X 50 115/230§ 115.0 N-53M ...

Page 3

... Type Primary Volts Section No. VA Voltage ±5% N-57MG 500 115 115.0 A N-257MG 500 230 115.0 N-59M 1,000 115 115.0 B N-59MG 1,000 115 115.0 N-259MG 1,000 230 115.0 With ground wire Mounting hole sizes: ( " Line cord, plug and receptacle are U.L. listed and verified to meet federal specifications. ...

Related keywords