Description
Transformers SPLIT PRI 150VA XFMR ISOLATION XFMR
Manufacturer
Triad Magnetics
Type
Transformers and Autotransformersr
Datasheets

Specifications of N-67A

Power Rating
150 VA
Dimensions
83.34 mm W x 98.42 mm H
Product
Isolation Transformers
Height
98.42 mm
Width
83.34 mm
Brand/series
N Series
Capacity
150 VA
Configuration
Enclosed
Current, Secondary
1.3 A
Frequency
50/60 Hz
Hipot Rating
1500 V (RMS)
Length, Lead
10 "
Mounting Hole Centers
2.5 "
Mounting Type
Panel/Chassis
Number Of Outlets
1
Phase
1
Power, Rating
150 VA
Standards
UL Listed
Termination
Leadwires
Voltage, Primary
115/230 VAC
Voltage, Rating
115⁄230 V
Voltage, Secondary
115 VAC
Weight
7 lbs.
Primary Voltages
115 / 230V
Secondary Voltages
115 VAC
Current Rating
1.3A
Transformer Mounting
Chassis
Secondary Current Nom
1.3A
Peak Reflow Compatible (260 C)
Yes
Rohs Compliant
Yes
Terminal Type
Leaded
Input Voltage
115VAC
Leaded Process Compatible
Yes
Output Current
1.3A
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
N-67A
Electrical Specifications (@25°C)
1. Maximum Power:
2. Input Voltage:
3. Output Voltage:
4. Full Secondary Load:
5. Voltage Regulation:
Description:
The N-67A is power transformer for isolating equipment from direct connection to the
power line. It is constructed with nonconcentrically wound coils. The primary and
secondary are wound on separate arbors, then assembled on a laminate core
side-by-side separated by insulation. This prevents electrical connection under
normal or overload conditions between the primary and secondary windings.
Safety:
These units are designed with 1500V isolation between winding to winding and
between winding and core. Materials and construction are rated for Class B
insulation system.
Dimensions:
3.875
Weight: 7.0 Lbs.
Mounting Holes: .375 x .187”
Connections: 10.0±1” leads, 0.250±0.062” Skin & Tin
Schematic:
INPUT - Series: BLK to BLK/GRN, JUMPER BLK/YEL to BLK/RED
OUTPUT: RED to RED
SHIELD: WHT
RoHS Compliance: As of manufacturing date February 2005, all standard products meet the
requirements of 2002/95/EC, known as the RoHS initiative.
A
Parallel: BLK to BLK/YEL, JUMPER BLK to BLK/RED and BLK/YEL to BLK/GRN
3.281
B
Parallel: 115V@50/60Hz
Series:230V@50/60Hz
3.875
C
2.50
BLK/GRN
D
BLK/RED
BLK/YEL
150 VA
115V + 5%
1.3 Amps RMS
5 % TYP @ full load to no load
BLK
3.00
Unit: In inches
E
2.00
F
RED
RED
WHT
SHIELD
P
C
HASSIS
O W E R
M
T
OUNT :
R A N S F O R M E R
Isolation
SH LEAD
A
SEC LEADS
E
F
C
D
B
PRIMARY
LEADS

Related parts for N-67A

N-67A Summary of contents

Page 1

... Voltage Regulation TYP @ full load to no load Description: The N-67A is power transformer for isolating equipment from direct connection to the power line constructed with nonconcentrically wound coils. The primary and secondary are wound on separate arbors, then assembled on a laminate core side-by-side separated by insulation. This prevents electrical connection under normal or overload conditions between the primary and secondary windings ...

Page 2

... E N-77U* 100 115/230 115.0 N-54M 150 115 115.0 N-54MG 150 115` 115.0 F N-73A 150 115 115/230§ N-67A 150 115/230§ 115.0 N-55M 250 115 115.0 N-55MG 250 115 115.0 G N-255MG 250 230 115.0 N-66A 250 115/230§ 115.0 ...

Page 3

... Type Primary Volts Section No. VA Voltage ±5% N-57MG 500 115 115.0 A N-257MG 500 230 115.0 N-59M 1,000 115 115.0 B N-59MG 1,000 115 115.0 N-259MG 1,000 230 115.0 With ground wire Mounting hole sizes: ( " Line cord, plug and receptacle are U.L. listed and verified to meet federal specifications. ...

Related keywords