63-13-115-6 SOLA HEVI DUTY, 63-13-115-6 Datasheet - Page 4

Power Conditioning 150VA 120V In/Out

63-13-115-6

Manufacturer Part Number
63-13-115-6
Description
Power Conditioning 150VA 120V In/Out
Manufacturer
SOLA HEVI DUTY
Series
MCRr
Datasheets

Specifications of 63-13-115-6

Output Voltage
120 V
Output Power
150 VA
Input Voltage (nominal)
120 V
Features
Harmonic Filtering
Mounting Type
Surface Mount
Input Voltage
120 V
Number Of Outlets
4
Voltage Regulation
+/- 3 %
Voltage Regulation Accuracy
+/- 3 %
Suppressor Type
Power Line Conditioner
No. Of Outlets
4
Width
177.8mm
Height
152.4mm
Output Type
Fixed
External Height
6.00"
Attenuation
120 dB (Common Mode), 60 dB (Transverse Mode)
Depth
9 in.
Power, Rating
150 VA
Standards
CSA Certified, UL Listed
Temperature, Operating
-20 to +40 °C
Weight
21 lbs.
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Operating Characteristics of the CVS & MCR Series
Regulation
Sola/Hevi-Duty’s CVS pow er con di tion ers will hold output
volt ag es to ±1.0% or less with input vari a tions as great as
±15% (115V ±15% or 120 V +10%/-20%). Units op er at ed at
less than rat ed load will maintain ap prox i mate ly ±1% regula-
tion over a wider input line volt age variation. Output meets
NEMA voltage specifi cations even when input voltage drops
to 65% of nominal. The output versus input voltage re la -
tion ship for a typical CVS is show in Figure A.
Note: MCR line regulations: ±3% for 60 Hz; ±5% for 50 Hz.
The typical per for manc es shown in Figure B indicate that
most of the residual changes take place near the lower
(95 V) and upper (130 V) ends of the input range. It is
possible to improve output regulation if line variations remain
within a restricted range near the center of the nameplate
range (for example, 100-120 V).
Normally, the output voltage will rise as the load is
decreased. Typical percentages for changes in resistive
load from full to zero load as shown below.
Except as noted, all characteristics of Sola/Hevi-Duty’s CVS products also
Figure B: Line Regulation
apply to the MCR series.
Figure A: Load Variation
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solaheviduty.com.
Power Protection and Conditioning
Input Characteristics
Sola/Hevi-Duty power conditioners include a resonant
circuit that is energized whether or not it is serving load. The
input current at no load or light load may run 50% or more
of the full primary current. As a result, the tem per a ture of the
unit may rise to substantially full-load level, even at light or no
load. Input power factor will average 90-100% at full load,
but may drop to about 75% at half load and 25% at no load.
In any case, the current is always leading. The input no load
watts are about 12.5% of the VA rating.
Frequency
Output voltage varies linearly with a change of fre quen cy of
the input voltage. This change is about 1.5% of the
output voltage for each 1% change in input frequency and in
the same direction as the frequency change.
Power Factor
Sola/Hevi-Duty power conditioners regulate any power factor
load. Output voltage is a function of load current and load
power factor (see Figure C). If lower voltage under lagging
power factor is objectionable, correction may be made with
ca pac i tors at the load. “Median” value of output voltage will
vary from the name plate rating if the load has a power
factor other than that for which the trans form er was
designed. Load regulation will also be relatively greater as
the in duc tive load power factor is decreased (see Figure C).
However, the resulting median values of output voltage will
be reg u lat ed against supply line chang es at any rea son able
load or load power factor.
Conditioner
Rating - VA
250 & over
60 & 120
CVS
30
Increase in Output
Load Removal
Voltage due to
3%
2%
1%
1
35