2866514 Phoenix Contact, 2866514 Datasheet

no-image

2866514

Manufacturer Part Number
2866514
Description
DIODE REDUNDANCY MODULE 24VDC
Manufacturer
Phoenix Contact
Series
Trior
Datasheet

Specifications of 2866514

Accessory Type
Redundancy Module
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With/related Products
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
TRIO-DIODE/12-24DC/2X10/1X20
Redundancy module
INTERFACE
Data sheet
104278_en_00
1
TRIO DIODE is the DIN-rail mountable redundancy module
from the TRIO POWER product range.
Using the redundancy module, it is possible for two power
supply units of the same type connected in parallel on the
output side to increase performance or for redundancy to be
100% isolated from one another.
Redundant systems are used in systems that place
particularly high demands on operational reliability. The
connected power supply units must be large enough that the
total current requirements of all loads can be met by one
power supply unit. The redundant structure of the power
supply therefore ensures long-term, permanent system
availability.
In the event of an internal device fault or failure of the mains
power supply on the primary side, the other device
automatically takes over the entire power supply of the loads
without interruption. The floating signal contact and LED
immediately indicate the loss of redundancy.
Description
Make sure you always use the latest documentation.
It can be downloaded from the product at www.phoenixcontact.net/catalog.
© PHOENIX CONTACT 2010-04-23
Features
100% decoupling of power supply units connected in
parallel
Reliable signaling of redundancy
Load currents up to 30 A supported
Easy, space-saving DIN rail mounting
High level of safety with regard to supply due to MTBF >
10 million h
Reverse polarity protection

Related parts for 2866514

2866514 Summary of contents

Page 1

... The floating signal contact and LED immediately indicate the loss of redundancy. Make sure you always use the latest documentation. It can be downloaded from the product at www.phoenixcontact.net/catalog. © PHOENIX CONTACT 2010-04-23 Features – 100% decoupling of power supply units connected in parallel – ...

Page 2

... Table of contents 2 Table of Contents 1 Description .................................................................................................................................. Features.....................................................................................................................................................................1 2 Table of contents......................................................................................................................... 3 Ordering data .............................................................................................................................. 4 Technical data............................................................................................................................. 5 Structure...................................................................................................................................... 6 Block diagram ............................................................................................................................. 7 Safety and warning notes ............................................................................................................ 8 Installation ................................................................................................................................... 9 Installation position...................................................................................................................... 10 Mounting on DIN rails .................................................................................................................. Assembly ...................................................................................................................................................................8 Removing...................................................................................................................................................................8 11 Input ............................................................................................................................................ 12 Output ......................................................................................................................................... 13 Function ...................................................................................................................................... Input/output ................................................................................................................................................................9 Signaling ..................................................................................................................................................................10 Thermal behavior .....................................................................................................................................................10 104278_en_00 TRIO-DIODE/12-24DC/2X10/1X20 PHOENIX CONTACT ...

Page 3

... Max. permissible relative humidity (operation) Vibration (operation) Shock Pollution degree in acc. with EN 50178 Climatic class 104278_en_00 TRIO-DIODE/12-24DC/2X10/1X20 Type Order No. TRIO-DIODE/12-24DC/2X10/1X20 2866514 ... ... Approx. 0 (-25°C to +55° (-25°C to +55° (-25°C to +40° (-25°C to +40°C) From +55°C to 70°C: 2.5% per Kelvin > Varistor Yes, with integrated diode, < ...

Page 4

... Conductor to conductor) Comments Criterion B EN 61000-4-6 Input/output Level 3 Frequency range 150 kHz ... 80 MHz Voltage 10 V Comments Criterion A EN 55011 (EN 55022) Class B, area of application: Industry and residential EN 55011 (EN 55022) Class B, area of application: Industry and residential TRIO-DIODE/12-24DC/2X10/1X20 PHOENIX CONTACT 4 ...

Page 5

... DC output approximately 0.5 V < DC input 6 Universal snap-on foot for EN DIN rails 6 solid Input 0.2 - 2.5 0.2 - 2.5 Output 0 Signal 0.2 - 2.5 0 ... ... Screw connection 9 mm 0.5 V < DC input Screw connection [mm ] AWG [Nm] stranded Torque 0.4 - 0.5 0 0 0.4 - 0.5 5 PHOENIX CONTACT ...

Page 6

... Before startup please ensure: The connection must be carried out by a competent person and protection against electric shock guaranteed. All input and output lines are dimensioned according to the maximum output current of the device or separately protected. Sufficient convection must be guaranteed. 104278_en_00 TRIO-DIODE/12-24DC/2X10/1X20 + + PHOENIX CONTACT ...

Page 7

... To ensure sufficient convection, we recommend the following minimum spacing be used between modules for vertical installation and 0 cm for horizontal installation. The redundancy module can be snapped onto all DIN rails in accordance with EN 60715 and must be mounted horizontally (connecting terminal blocks on top and bottom). PHOENIX CONTACT 7 ...

Page 8

... You can fasten the connection cables to the housing using cable binders. Make sure that the connecting cables and cable binders used are designed for the surface temperatures on the housing. When tightening the cable binders, the insulation of the connecting cables must not be damaged. PHOENIX CONTACT 8 ...

Page 9

... This is necessary because the maximum current carrying capacity per input must not be exceeded. For connecting the redundancy module to the power supply unit, OUT+ we recommend using two identical connecting cables (cable length/cable cross sections). TRIO-DIODE/12-24DC/2X10/1X20 PHOENIX CONTACT 9 ...

Page 10

... PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00 104278_en_00 PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300 Signaling A floating relay contact and "Redundancy OK" LED are available for monitoring redundancy. In normal operation where input voltage > ...

Related keywords