Specifications of LC1D12F7

No. Of Poles
3
Contact Configuration
3PST-NO
Relay Mounting
DIN Rail
Coil Voltage Vac Nom
110V
Contact Voltage Ac Max
600V
Width
45mm
Relay Terminals
Screw Clamp
Contact Current Ac Max
25A
Height
77mm
Operating Voltage
600VAC
Switching Power Ac1
2hp
Switching Power Ac3
10hp
Switching Current Ac1
25A
Switching Current Ac3
12A
Load Current Inductive
12A
Load Current Resistive
25A
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Control of 3-phase
asynchronous squirrel
cage motors with
breaking while motor
stalled.
The current broken
(Ic) in category AC-4
is equal to 6 times Ie,
where le is the
operational current
of the motor.
Use motor-locked
rotor current (6 times
full-load current) on
horizontal axis for
selection purposes.
Control of 3-phase
asynchronous squirrel
cage (AC-4) or slip-
ring (AC-2) motors
with breaking while
motor stalled.
The current broken
(Ic) in category AC-4
is equal to 6 times Ie,
where le is the
operational current
of the motor.
Use motor-locked
rotor current (6 times
full-load current) on
horizontal axis for
selection purposes.
Contactor Selection for Utilization Categories AC-2 and AC-4
26
©
2001-2004 Schneider Electric All Rights Reserved
Use in Categories AC-2 or AC-4 (Ve
NOTE: The dotted lines relate to LC1K12 and LP1K12 contactors only.
Example: Asynchronous motor with P = 5.5 kW – Ve = 400 V – Ie = 11 A
Use in Category AC-4 (440 Vac < Ve
0.08
0.06
0.05
0.04
0.03
0.02
0.01
0.08
0.06
0.05
0.04
0.03
0.02
0.01
0.8
0.6
0.4
0.2
0.1
0.8
0.6
0.4
0.2
0.1
1
1
5
5
6 7
6 7
Asynchronous motor with P = 5.5 kW – Ve = 415 V – Ie = 11 A
200,000 operating cycles required.
The above selection curves show the contactor rating needed: LC1D25 or LP1D25.
8 9 10
8 9 10
20
20
30
30 36 40
440 Vac)
40
690 V)
50
50 54
70
72
80
90
105
108
150 170 210 250 300
150 192 240 300
400 500
lc = 6 x le = 66 A; or
lc = 6 x le = 66 A.
390 480
Current broken in A
540
Current broken in A
570
640 800 1000
630
828 1000
01/04