LC1D09GD SQUARE D, LC1D09GD Datasheet - Page 62

IEC Contactor

LC1D09GD

Manufacturer Part Number
LC1D09GD
Description
IEC Contactor
Manufacturer
SQUARE D
Datasheet

Specifications of LC1D09GD

No. Of Poles
3
Contact Configuration
3PST-NO
Relay Mounting
DIN Rail
Coil Voltage Vdc Nom
125V
Relay Terminals
Screw Clamp
Width
45mm
Coil Resistance
717ohm
Nom Operating Power
5.5kW
External Width
45mm
Operating Voltage
600VAC
Switching Power Ac1
1hp
Switching Power Ac3
7.5hp
Switching Current Ac1
25A
Switching Current Ac3
9A
Load Current Inductive
9A
Load Current Resistive
25A
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Characteristics of Type LR•K Overload Relays
62
©
2001-2004 Schneider Electric All Rights Reserved
Electrical Characteristics of the Power Circuit
Operating Characteristics
Rated operational voltage (Ve)
Rated insulation voltage (Vi)
Rated impulse withstand voltage (Vimp)
Frequency limits of the operational current
Power dissipated per pole
Short-circuit protection and coordination
Sensitivity to phase failure
Reset
Signalling
Reset-Stop function
Test function
Tripping curves
Average operating time
related to multiples of the
current setting Class 10 A
Balanced 3-phase operation, from cold state.
1h 20 min
Time
40 min
20 min
10 min
6 min
4 min
2 min
1 min
40 s
20 s
10 s
2 h
1 h
6 s
4 s
2 s
1 s
1 1.2 1.5
Up to
Conforming to BS 4941
Conforming to IEC 60947
Conforming to VDE 0110 group C
Conforming to UL 508, CSA 22.2 No. 14
By circuit breaker
By fuses
Conforming to IEC 60947
Manual or automatic
On front of relay
By pushbutton
2
3
4
x setting current (Ir)
5 6
Class 10 A
8 10
15
1h 20 min
V
V
V
V
V
kV
Hz
W
Balanced operation with 2-phases only, from cold state.
1 = Setting: at lower end of scale.
2 = Setting: at upper end of scale.
40 min
20 min
10 min
Time
6 min
4 min
2 min
1 min
40 s
20 s
10 s
2 h
1 h
6 s
4 s
2 s
1s
690
690
690
750
600
6
Up to 400
2
Select in accordance with NEC and local codes
Maximum 400% of motor FLA
Yes
Selected by means of a lockable and sealable switch
on the front of the relay
Trip indicator
Pressing the Reset-Stop button:
– Actuates the N.C. contact
– Has no effect on the N.O. contact
Pressing the Test button enables:
– Checking of the control circuit wiring
– Simulation of overload tripping (actuation of both
1 1.2 1.5
N.C. and N.O. contacts, and of the trip indicator)
2
3
4
x setting current (Ir)
5 6
Class 10 A
8 10
1
2
15
01/04