XTCE018C10TD EATON CUTLER HAMMER, XTCE018C10TD Datasheet - Page 74

CONTACTOR, SPST-NO, 24VDC, 18A, DIN RAIL

XTCE018C10TD

Manufacturer Part Number
XTCE018C10TD
Description
CONTACTOR, SPST-NO, 24VDC, 18A, DIN RAIL
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of XTCE018C10TD

No. Of Poles
3
Contact Configuration
SPST-NO
Relay Mounting
DIN Rail
Coil Voltage Vdc Nom
24V
Relay Terminals
Screw Clamp
Coil Voltage Dc Min
24V
Nom Operating Power
11kW
Operating Voltage
690VAC
Switching Power Ac1
3hp
Switching Power Ac3
15hp
Switching Current Ac1
40A
Switching Current Ac3
18A
Load Current Inductive
18A
Load Current Resistive
40A
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
34
34-74
Frame L – R
Table 34-115. Coil Data — Frame L – R
Voltage Tolerance
Power Consumption of the coil at cold state and 1.0 x U c
Switching Time at 100% Main Contact U c (approximate values)
Reaction in Threshold and Sealing State Transition Range (XTCE185L – XTCEC20R)
Description
Pick-Up (x U c )
Drop-Out (x U c )
XTCE185L – XTCEC20R
XTCS185L – XTCS500M
Duty Factor (%DF)
XTCE185L – XTCEC20R
XTCS185L – XTCS500M
Voltage interruptions
Permissible contact resistance (of the external
command device with actuation of A11), Ω
Permissible residual current (with actuation of
A11 by the electronics with 0 signal)
SPS Signal Level (A3 – A4) to
IEC/EN 61131-2 (Type 2)
Electromagnetic compatibility (EMC)
Voltage Dips
Excess Voltage
Pick – Up phase
XTCE185L – XTCEC20R
XTCS185L – XTCS500M
XTCE185L – XTCEC20R
XTCS185L – XTCS500M
Pick-Up VA
Pick-Up W
Sealing VA
Sealing W
Pick-Up VA
Pick-Up W
Sealing VA
Sealing W
Closing delay (mS)
Opening delay (mS)
Closing delay (mS)
Opening delay (mS)
High
Low
(0 – 0.2 x U cmin ) ≤ 10ms
(0 – 0.2 x U cmin ) > 10ms
(0.2 – 0.6 x U cmin ) ≤ 12ms
(0.2 – 0.6 x U cmin ) > 12ms
(0.6 – 0.7 x U cmin )
(0 – 0.7 x U cmin )
(0.7 x U cmin –1.15 x U cmax )
Control transformer with U k ≤6%.
(1.15 – 1.3 x U cmax )
(>1.3 x U cmax ) ≤ 3s
(>1.3 x U cmax ) > 3s
(>1.15 x U cmax )
IEC Contactors & Starters
XT IEC Power Control
Contactors and Starters
XTCE185L, XTCS185L
250
200
4.3
3.3
360
325
4.3
3.3
100
<100
<80
<50
<40
≤500
≤1
15V
5V
This product is designed for operation in industrial environments. Usage in domestic areas can cause radio
frequency interference (RFI). Noise suppression measures must be provided for the additional interference.
For more information visit: www.eaton.com
XTCE225L, XTCE250L,
XTCS250L
250
200
4.3
3.3
360
325
4.3
3.3
100
<100
<80
<50
<40
≤500
≤1
15V
5V
Contactor switches on with certainty
Contactor switches on with certainty
Contactor remains switched on
Contactor remains switched on
Contactor remains switched on
Contactor does not switch on
0.7 x U cmin — 1.15 x U cmax
0.85 x U cmin — 1.1 x U cmax
Time is bridged successfully
Time is bridged successfully
0.2 x U cmin — 0.6 x U cmax
0.2 x U cmin — 0.4 x U cmax
Drop-out of the contactor
Drop-out of the contactor
Drop-out of the contactor
XTCE300M, XTCE400M,
XTCS300M
450
350
4.3
3.3
715
645
4.3
3.3
100
<80
<80
<50
<40
≤500
≤1
15V
5V
XTCE500M, XTCS500M,
XTCE570M, XTCS570M
450
350
4.3
3.3
715
645
4.3
3.3
100
<80
<80
<50
<40
≤500
≤1
15V
5V
CA08102001E
March 2009

Related parts for XTCE018C10TD