K8ABAS2200230VAC Omron, K8ABAS2200230VAC Datasheet - Page 3

RELAY, CURRENT, 0.1-8A

K8ABAS2200230VAC

Manufacturer Part Number
K8ABAS2200230VAC
Description
RELAY, CURRENT, 0.1-8A
Manufacturer
Omron
Series
K8ABr
Datasheet

Specifications of K8ABAS2200230VAC

Contact Configuration
SPDT
Power Consumption
5VA
Supply Voltage Max
230VAC
Contact Current Max
6A
Relay Mounting
DIN Rail
Svhc
No SVHC (15-Dec-2010)
Contact Current Ac Max
6A
Ratings and Specifications
■ Ratings
■ Specifications
Cat. No. N142-E1-01
Operating power
Operate (SV)
Reset (HYS.)
Operating time (T)
Operating power ON lock (LOCK)
Setting accuracy
Time error
Input frequency K8AB-AS1/AS2
Continuous
input
Input impedance
Indicators
Output relays
Ambient operating temperature
Storage temperature
Ambient operating humidity
Storage humidity
Altitude
Operating voltage range
Rated power supply frequency
Output relays
Terminal screw tightening torque
Crimp terminals
Insulation resistance
Resistive load
Inductive load
Minimum load
Maximum contact voltage 250 VAC
Maximum contact current 6 A AC
Maximum switching
capacity
Mechanical life
Electrical life
Non-isolated power supply
Isolated power supply
Operating value setting
range
Operating value
Hysteresis
Resetting method
K8AB-AS3
K8AB-AS1/AS2
K8AB-AS3
− 20 to 60°C (with no condensation or icing)
− 40 to 70°C (with no condensation or icing)
25% to 85%
25% to 85%
2,000 m max.
85% to 110% of rated operating voltage
50/60 Hz ±5 Hz (AC power supply)
6 A at 250 VAC (cos φ = 1)
6 A at 30 VDC (L/R = 0 ms)
1 A at 250 VAC (cos φ = 0.4)
1 A at 30 VDC (L/R = 7 ms)
10 mA at 5 VDC
1,500 VA
10,000,000 operations
Make: 50,000 times, Break: 30,000 times
1.2 N·m
Two solid wires of 2.5 mm
tightened together
20 M Ω (at 500 V) between charged terminals and exposed uncharged parts
20 M Ω (at 500 V) between any charged terminals (i.e., between input, output, and power supply
terminals)
24 VDC (1 W)
24 VAC (3 VA), 100 to 115 VAC (4 VA), 200 to 230 VAC (5 VA)
10% to 100% of maximum rated input value
100% operation at set value
5% to 50% of operating value
Manual reset/automatic reset (switchable)
Manual reset: Turn OFF operating power for 1 s or longer.
0.1 to 30 s (Value when input rapidly changes from 0% to 120%.)
0 to 30 s (Value when input rapidly changes from 0% to 120%; lock timer starts when input
reaches approximately 30% of set value.)
±10% of full scale
±10% of set value (Minimum error: 50 ms)
DC input, 45 to 65 Hz
45 to 65 Hz
Continuous input: 115% of maximum input, 10 s max.: 125% of maximum input
Continuous input: 240 A, 30 s max.: 400 A, 1 s max.: 1,200 A
5 Ω max.
Power (PWR): Green LED, Relay output (RY): Yellow LED, Alarm outputs (ALM): Red LED
One SPDT relay (6 A at 250 VAC, resistive load)
2
, two crimp terminals of 1.5 mm
Single-phase Current Relay
2
with insulation sleeves, can be
K8AB-AS
3