LY2 220/240 VAC Omron, LY2 220/240 VAC Datasheet - Page 4

RELAY, PLUG-IN, DPCO, 240VAC

LY2 220/240 VAC

Manufacturer Part Number
LY2 220/240 VAC
Description
RELAY, PLUG-IN, DPCO, 240VAC
Manufacturer
Omron
Datasheet

Specifications of LY2 220/240 VAC

Relay Type
General Purpose
Coil Voltage Vac Nom
240V
Contact Current Max
10A
Contact Voltage Ac Nom
110V
Contact Voltage Dc Nom
24V
Coil Resistance
15.97kohm
Coil Type
AC Coil
Coil Current
5.3mA
Contact Configuration
DPCO
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
■ Contact Ratings
*Note: P level:
■ Characteristics
Note: 1. The values given above are initial values.
A-34
Load
Rated load
Rated carry
current
Max.
switching
voltage
Max.
switching
current
Max.
switching
power
Failure rate
(reference
value)*
Contact resistance
Operate time
Release time
Max. operating frequency
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Endurance
Ambient temperature*
Ambient humidity
Weight
Relay
2. The upper limit of 40 C for some Relays is because of the relationship between diode junction temperature and the element used.
General-purpose Relay
110 VAC 15 A
24 VDC 15 A
15 A
250 VAC
125 VDC
15 A
1,700 VA
360 W
100 mA, 5 VDC
60
Item
= 0.1 x 10
Resistive load
(cos = 1)
-6
/operation, reference value
1-pole
110 VAC 10 A
24 VDC 7 A
1,100 VA
170 W
Inductive load
50 m max.
25 ms max.
25 ms max.
Mechanical:
Electrical:
100 M
1,000 VAC, 50/60 Hz for 1 min between contacts of same polarity
2,000 VAC, 50/60 Hz for 1 min between contacts of different polarity
Destruction:
Malfunction:
Destruction:
Malfunction:
Mechanical:
Electrical:
Operating:
Single- and double-pole standard, bifurcated-contact Relays: –25 C to 55 C (with no icing)
(–25 C to 70 C if carry current is 4 A or less)
All other Relays: –25 C to 40 C (with no icing) (–25 C to 55 C if carry current is 4 A or less)
Operating:
Single- and double-pole: approx. 40 g, three-pole: approx. 50 g, four-pole: approx. 70 g
(cos =0.4,
L/R=7 ms)
LY
All except Relays with bifurcated contacts
Single contact
min. (at 500 VDC)
AC:
DC:
Single-, three-, and four-pole: 200,000 operations min. (at 1,800 operations/hr
under rated load)
Double-pole: 500,000 operations min. (at 1,800 operations/hr under rated load)
18,000 operations/hr
1,800 operations/hr (under rated load)
10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)
10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)
1,000 m/s
200 m/s
5% to 85%
110 VAC 10 A
24 VDC 10 A
10 A
250 VAC
125 VDC
10 A
1,100 VA
240 W
100 mA, 5 VDC
Resistive load
50,000,000 operations min. (at 18,000 operations/hr)
1,00,000,000 operations min. (at 18,000 operations/hr)
(cos = 1)
2
2
2-, 3- or 4-pole
110 VAC 7.5 A
24 VDC 5 A
825 VA
120 W
Inductive load
(cos =0.4,
L/R=7 ms)
110 VAC 5A
24 VDC 5 A
7 A
250 VAC
125 VDC
7 A
550 VA
120 W
10 mA, 5 VDC
Relays with bifurcated contacts
Resistive load
(cos = 1)
Bifurcated contacts
2-pole
110 VAC 4 A
24 VDC 4A
440 VA
100 W
Inductive load
(cos =0.4,
L/R=7 ms)

Related parts for LY2 220/240 VAC