D6DI TELE, D6DI Datasheet - Page 2

ASYMMETRIC FLASHER, 1 CO

D6DI

Manufacturer Part Number
D6DI
Description
ASYMMETRIC FLASHER, 1 CO
Manufacturer
TELE
Datasheet

Specifications of D6DI

Contact Configuration
SPCO
Nom Input Voltage
240VAC
Delay Time Range
50ms To 10days
Adjustment Type
Knob
Relay Mounting
DIN Rail
Svhc
No SVHC (18-Jun-2010)
Coil Voltage Vac Nom
250V
Contact Current Ac
RoHS Compliant
D6DI
Asymmetric flasher pause first (lp)
When the supply voltage U is applied, the set interval t1 begins (green
LED flashing slowly). After the interval t1 has expired, the output relay
R switches into on-position (yellow LED illuminated) and the set inter-
val t2 begins (green LED flashing fast). After the interval t2 has expired,
the output relay switches into off-position (yellow LED not illuminated).
The output relay is triggered at the ratio of t1:t2 until the supply voltage
is interrupted.
www.tele-power-net.com
Functions
Connections
Dimensions
Asymmetric flasher pulse first (li)
When the supply voltage U is applied, the output relay R switches
into on-position (yellow LED illuminated) and the set interval t1 begins
(green LED flashing slowly). After the interval t1 has expired, the output
relay switches into off-position (yellow LED not illuminated) and the
set interval t2 begins (green LED flashing fast). After the interval t2
has expired, the output relay switches into on-position (yellow LED
illuminated).
The output relay is triggered at the ratio of t1:t2 until the supply voltage
is interrupted.

Related parts for D6DI