253-TAAU-LSFA-C6 Tyco Electronics, 253-TAAU-LSFA-C6 Datasheet
253-TAAU-LSFA-C6
Specifications of 253-TAAU-LSFA-C6
Related parts for 253-TAAU-LSFA-C6
253-TAAU-LSFA-C6 Summary of contents
Page 1
... Safety Features Crompton transducers and transmitters are designed for use in harsh electrical environments and feature: • High protection against overload - 20 x rated current for 1 second. • High degree of mechanical shock and vibration resistance. • Protection against high voltage. Inputs, outputs and power supply are galvanically isolated from one another (excluding Resistance transmitters) ...
Page 2
... Paladin Transducers 250 Series Class 0.5 Specification Performance Designed to comply with BS6253 part 1, EN60688, IEC688, AS1384 and ANSI. C37. Temperature Range: Storage -20°C to +70°C Operating 0°C to +60°C Calibrated at 23°C Temperature Coefficient: 0.03%/ per °C Humidity Range 95% RH Zero Adjustment: ± ...
Page 3
... Product Code – 3 Phase Current Transducers - 3 D.C. Outputs Input A.C. A.C. Aux Power O/P D. 120V 0/1mA 120V 4/20mA With multiple analogue outputs, do not common the -ve terminals. 11 Catalogue No. Connection Diag. 253-TAA*-LSFA-C6 1 Catalogue No. Connection Diag. 256-TAA-LSFA-C6 47 Catalogue No. Connection Diag. 253-TAL*-LSHG-C6-DG 6 Catalogue No. Connection Diag. 256-TAS*-LSFA-C6-DG 2 256-TAL*-LSHG-C6-DG 2 ...
Page 4
... Time Constant O/P D.C. 1mA 8 Minutes 0/1mA 1mA 15 Minutes 0/1mA 1mA 30 Minutes 0/1mA 12 Catalogue No. Connection Diag. 253-TAR*-LSFA-C6-DG 6 Catalogue No. Connection Diag. 256-TAR*-LSFA-C6-DG 2 Catalogue No. Connection Diag. 253-TAP*-LSFA-C6-DG 8 253-TAN*-LSFA-C6-DG 8 253-TAM*-LSFA-C6-DG 8 Catalogue No. Connection Diag. 253-TDP*-FAFA-DG 4 253-TDN*-FAFA-DG 4 253-TDM*-FAFA-DG 4 ...
Page 5
... Auxiliary Power: Self Powered Outputs: 0/1mA, 0/5mA, 0/10mA and 0/20mA Product Code – Single Phase, Self Powered, 1 D.C. Output Input A.C. Aux Power O/P D.C. 120V 60Hz Self 0/1mA 13 Catalogue No. Connection Diag. 256-TAB*-LSM1-C6-PQ-T3 3 Catalogue No. Connection Diag. 253-TVA*-PQFA-C6 10 ...
Page 6
... Product Code – Single Phase - Suppressed Zero - A.C. Voltage Transducer, Self Powered - 1 D.C. Output Input A.C. A.C.Aux Power O/P D.C. 108 - 132V Self 0/1mA 14 Catalogue No. Connection Diag. 253-TVL*-PQHG-C6-DG 15 Catalogue No. Connection Diag. 256-TVL*-PQHG-C6-DG 11 256-TVS*-PQFA-C6-DG 11 Catalogue No. Connection Diag. 253-TVZ*-A9FA-C6 15 ...
Page 7
... D.C. Output Input A.C. Frequency O/P D.C. 120V 45/55Hz 0/1mA 120V 55/65Hz 0/1mA 120V 45/65Hz 0/1mA 120V 360/440Hz 0/1mA 15 Catalogue No. Connection Diag. 253-TVR*-PQFA-C6-DG 15 Catalogue No. Connection Diag. 256-TVR*-PQFA-C6-DG 11 Catalogue No. Connection Diag. 253-THZ*-PQFA-AG 10 253-THZ*-PQFA-AN 10 253-THZ*-PQFA-AJ 10 253-THZ*-PQFA-BI 10 ...
Page 8
... Product Code – Side Wire Transmitter (3 wire), Auxiliary Powered Input A.C. Aux Power O/P D.C. (Specify) R1, R2, R3 120V 0/1mA 16 Catalogue No. Connection Diag. 253-TRT*-TIFA-DG 12 253-TRT*-T5FA-DG 12 Catalogue No. Connection Diag. 253-TRP*-TRFA-DG 12 ...
Page 9
... I out x R Load limited to 15V Input Voltage: Typically I x (load + 200Ω) limited to 18V UL File Number: E149713N CSA File Number: LR52592 Product Code – Signal Isolator Input D.C. O/P D.C. 20mA 0/20mA 17 Catalogue No. Connection Diag. 253-TIK*-FAPO-DG 13 Catalogue No. Connection Diag. 250-ISA*-HF 5 ...
Page 10
... Copper: 2Ω minimum span, 20Ω maximum span Nickel: 20Ω minimum span, 200Ω maximum span 18 Catalogue No. Connection Diag. 256-TTA*-**FA-DG 18 256-TTM*-**FA-DG 18 256-TTV*-**FA-DG 18 256-TTN*-KTFA-DG 18 256-TTC*-TTFA-DG 18 256-TTF*-JTFA-DG 18 Catalogue No. Connection Diag. 253-TRR*-R1FA-DG 17 253-TRR*-R2FA-DG 17 ...
Page 11
... Square wave pulses from a multi-vibrator circuit with a mark-space ratio varied by the measured voltage, and amplitude varied by the measured current, are fed to an integrator and an output amplifier circuit. The D.C. milliamp signal produced is therefore directly proportional to the power input ...
Page 12
Paladin Transducers 250 Series Class 0.5 Power Factor and Phase Angle A range of power factor and phase angle transducers with a linearised output. Product Codes – Power Factor Transducer (for Digital Meters & Systems) 3 Phase ...