ACF-3000DM-A Amprobe, ACF-3000DM-A Datasheet
ACF-3000DM-A
Specifications of ACF-3000DM-A
Related parts for ACF-3000DM-A
ACF-3000DM-A Summary of contents
Page 1
... Current measurement from 15A to 3000Afor each of the three phases 4 Neutral wire current measurement down to milliamps 4 Flexible head fits all small conductors and large bus-bars up to 7” in diameter 4 Recommended one ACF-3000 SR for single phase system, and three for three phase systems 4 Output Sensitivity (AC coupled): 0.333 mV per Amp 4 Safety: CATIII 600 ...
Page 2
... Storage Temperature Range............. -40 to 221º F (-40 to +105º C) head ..................................................................: -4 to 185º F (-20 to +85º C) electronics Operating Humidity.............................................: 15% to 85% (non condensing) Weight.............................................................:0.40 Lb (180 g) head, The ACF-3000 current probe utilising the Rogowski principle. It can be used to measure currents up to 3000A. * Specifications subject to change without notice Safety Standards Safety Standards BSEN61010-1: 1993, 600V Cat III, Pol ...