P11131000072A BARBER - COLMAN, P11131000072A Datasheet - Page 7

Thermocouple

P11131000072A

Manufacturer Part Number
P11131000072A
Description
Thermocouple
Manufacturer
BARBER - COLMAN
Type
J Typer
Datasheet

Specifications of P11131000072A

Lead Length
72"
Thermocouple Type
J
Terminal Type
Stripped Lead
Probe Length
72 In
Features
Locking Cap
Lead Free Status / RoHS Status
na
Analyzing a Model Number (continued)
HA136712
Fields 2 and 3
Field 4
Field 5
Field 6
Field 7
Fields 8 and 9
Fields 10, 11 and 12
Fields 14 and 15
Model Number Breakdown
Element
Two wires of dissimilar alloys joined at the tip. When the ends are exposed to a temperature
gradient, and electromotive force (EMF) is generated. The EMF is very small, amounting
to microvolts per degree.
Element Configuration
This field indicates either single or dual element in a straight, 45° angle, or 90° angle tube.
Probe Diameter
This code indicates either a 1/8" diameter or a 3/16" diameter.
Junction Style and Protection
This field indicates closed or open end, ground or ungrounded junction, and with or without
flexible armor.
Cold End Termination
Specifies stripped ends, lugs, plug and/or jack.
Rigid Length or Melt Bolt Length
This field specifies the rigid length of the probe (dimension "X") of those sensors with an
adjustable attaching device; or the length of a melt bolt style sensor.
Flexible Length
This is the flexible length (dimension "Y") of the thermocouple. It is the entire length of the
spring style Varidepth sensor, or the flexible portion behind the rigid portion of other
assemblies. Flexible length may be fiberglass insulated, or clad with stainless steel overbraid
or flexible armor.
Immersion Depth
This code defines how the sensor interacts with the measured media. It defines the
immersion depth (dimension "Z" ) of a typical sensor or the tip length (dimension "T") of
a melt bolt sensor. Or, it defines the size of the ring or lug on the ring/lug style sensor.