H3BA-N 110 VAC Omron, H3BA-N 110 VAC Datasheet - Page 8

Multi Timer 11 Pin

H3BA-N 110 VAC

Manufacturer Part Number
H3BA-N 110 VAC
Description
Multi Timer 11 Pin
Manufacturer
Omron
Datasheet

Specifications of H3BA-N 110 VAC

Time Range
0.05s To 300hr
Power Consumption
1.6W
Reset Time
0.1s
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
H3BG-N8
Engineering Data
8
Accuracy of operating time
Setting error
Star-delta transfer time
Influence of voltage
Influence of temperature
Insulation resistance
Dielectric strength
Impulse withstand voltage
Noise immunity
Static immunity
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Life expectancy
Case color
Enclosure ratings
Weight
Characteristics
10,000
5,000
1,000
500
100
250 VAC (cosf = 0.4)
Load current (A)
30 VDC L/R = 7 ms
250 VAC/30 VDC
(cosf = 1)
±0.3% FS max.
±5% FS ±0.05 s max.
Accuracy: ±25% FS + 5 ms max.
±0.5% FS max.
±2% FS max.
100 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed
non-current-carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
3 kV (between power terminals)
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)
±1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width:
100 ns/1 µs, 1-ns rise)
Malfunction: 8 kV
Destruction: 15 kV
Destruction:10 to 55 Hz with 0.75-mm single amplitude each in three directions
Malfunction:10 to 55 Hz with 0.5-mm single amplitude each in three directions
Destruction: 1,000 m/s
Malfunction: 300 m/s
Operating:–10°C to 55°C (with no icing)
Storage: –25°C to 65°C (with no icing)
Operating: 35% to 85%
Mechanical:20 million operations min. (under no load at 1,800 operations/h)
Electrical:
Light Gray (Munsell 5Y7/1)
IEC: IP40 (panel surface)
H3BG-N8: Approx. 110 g; H3BG-N8H: Approx. 130 g
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosf = 1)
100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h)
2
(approx. 30G) each in three directions
2
and a maximum current of 0.1 A can be switched if L/R is 7 ms. In
both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 100 mA at 5 VDC (failure level: P).
(approx. 100G) each in three directions
H3BG-N8

Related parts for H3BA-N 110 VAC