C500-AP003 Omron, C500-AP003 Datasheet - Page 75

no-image

C500-AP003

Manufacturer Part Number
C500-AP003
Description
PROGRAMMING CONSOLE ADAPTER
Manufacturer
Omron
Datasheets

Specifications of C500-AP003

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Safety Considerations
Inductive Load Surge
Suppressor
Electrical Noise
62
When an inductive load is connected to an I/O Unit, connect a surge suppressor
or diode in parallel with the load as shown in the following diagram. This is so that
the back electromagnetic field generated by the load will be absorbed.
Take appropriate measures when any electrical device likely to produce noise is
connected to the PC as a load. Devices generating noise of more than 1,200 V
(such as electromagnetic relays and valves) require noise suppression. For
noise sources running on AC power, connect a diode in parallel with the coil of
each device.
When mounting a CPU Rack and an Expansion I/O Rack together on a mounting
plate, provide a solid ground to the mounting plate. The mounting plate must be
plated with a highly conductive surface in order to ensure noise immunity.
Relay Output Unit
Transistor Output Unit
Relay Output Unit
Triac Output Unit
Resistor:
Capacitor: 0.47 F
Voltage:
Diode:
than three times the load voltage and an av-
erage current of 1 A
50 W
200 V
Must withstand voltages of more
L
OUT
COM
OUT
COM
Surge suppressor
Diode
COM
L
Diode
L
IN
DC Input
+
Section 7

Related parts for C500-AP003