C500ID501CN Omron, C500ID501CN Datasheet - Page 29

no-image

C500ID501CN

Manufacturer Part Number
C500ID501CN
Description
TTL INPUT
Manufacturer
Omron
Datasheet

Specifications of C500ID501CN

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
No. Of Digital Inputs
32
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
I/O Power Supply
2-4
2-5
16
3G2A5-PS222-E
3G2A5-PS212-E
Model
I/O Power Supply
Expansion I/O Backplane
100 to 120/200 to 240
VAC (selectable)
24 VDC
Supply Voltage
Note Be sure to keep the total power consumed by all the Units mounted on a Rack
The Expansion I/O Backplane shown in the following diagram, can be used to
expand the C1000H and C2000H Simplex and Duplex Systems. An Expansion
I/O Rack is just like a CPU Rack, except a CPU is not mounted. However, a
Power Supply is needed for each Expansion I/O Rack. There are three models
of Expansion I/O Backplane available. The Expansion I/O Rack shown below
can only be used with C2000H Systems. This Backplane has a special slot for
the I/O Remove Unit, which allows on-line I/O Unit exchange. two models are
available for C1000H PCs, with either five or eight slots.
Just as a Power Supply must be mounted to the CPU Rack, a Power Supply
must also be mounted to the I/O Backplane and Expansion I/O Backplanes.
There are two Power Supplies available; 100 to 120/200 to 240 VAC and 24
VDC, both of which are explained below. For details, refer to Appendix B Specifi-
cations. Either Power Supply can be used in the C1000H or C2000H Simplex
Systems; however, the 24-VDC Power Supply can not be used in the C2000H
Duplex System.
within the value stated in the table above. For example, do not mount I/O Units
with a total current consumption of 7A to a Rack supplied by a 7 A Power Supply.
As shown in the table above, the available current for I/O Units is only 6.5 A. For
details concerning current consumption, refer to Section 4 System Connections.
Expansion I/O Backplane
7A 5 VDC
7 A 5 VDC
Output Capacity
I/O Interface Unit
An I/O Interface Unit must be mounted to an Expansion
I/O Rack in order to connect the Expansion I/O Rack to
another Expansion I/O Rack.
I/O Remove Unit
When mounted to the Rack, I/O Units can be
removed or mounted while the PC is operating.
I/O Units
6.5 A
6.5 A
Available Current for I/O
Units
Expansion I/O Power Supply
Provided
Not provided
24 VDC Output Terminal
Section 2-5