Wiring
5-5
Transmission Lines
66
Wiring
Master
+
1, 2, 3...
120
Masters, Slaves and Remote Interfaces are connected using 2-conductor
cable in the manner shown below.
1.
2.
3.
4.
5.
6.
7.
8.
All 2-conductor cable used for connections must be 0.75 mm VCTF (vi-
nyl cabtire fiber cable).
Connect positive to positive, negative to negative.
Do not wire a Master directly to more than one other Unit; i.e., start wir-
ing at each Master and continue in order through the last Unit at the
other end of each line.
Set the last Unit as the terminator.
Do not branch the wiring at a Slave; i.e., wire a Slave in series to a
maximum of two other Units, one before it and one following it.
The total cable length must be 200 meters or less from each Master to
its terminator.
Do not run transmission lines parallel to or in the vicinity of high-voltage
or high-current lines. (Running transmission lines with normal I/O lines
or normal power lines presents no problem.)
RS-485 interfaces are used for transmission lines, as shown below.
Master
Terminator switch OFF
+
Slave (Terminator switch ON)
+
Slave
Transmission
terminals
+
Terminator switch OFF
Slave
+
Slave (Terminator switch OFF)
Remote Interface
120
Terminator switch ON
+
Section 5-5