CV500BSC51 Omron, CV500BSC51 Datasheet - Page 58

no-image

CV500BSC51

Manufacturer Part Number
CV500BSC51
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500BSC51

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Executable Enhanced
BASIC Commands
OS (Output Status)
IN (Initialize)
ID0 (Input Data: ASCII)
ID1 (Input Data: Binary)
OD0 (Output Data: ASCII)
OD1 (Output Data: Binary)
Slave Mode Functions
Sends the Unit’s internal status (1 byte) to the host computer. The following
diagram shows the functions of the signals in the status byte.
BIN:
P.ERR: When this bit is “1”, it indicates that a parameter error has occurred.
C.ERR: When this bit is “1”, it indicates that a command error has occurred.
T.ERR: When this bit is “1”, it indicates that a timeout error has occurred.
G.ERR: When this bit is “1”, it indicates that a GP-IB interface error has
---:
This command returns the GP-IB Interface Unit to its initial status. Use this
command to initialize just the GP-IB Interface Unit.
When an ID0 command is received from the host computer, the rest of the
received data is treated as ASCII data. The data is converted to binary format,
and stored in the reception data area.
When an ID1 command is received from the host computer, the rest of the
received data is treated as binary data and stored unchanged in the reception
data area.
When an OD0 command is received from the host computer, the transmission
data format is set to ASCII. The data in the transmission data area is con-
verted to ASCII and sent. The Unit will continue to convert output data to
ASCII before sending it unless an OD1 command is received.
When an OD1 command is received from the host computer, the transmission
data format is set to binary. The data in the transmission data area is sent
unchanged in binary format. The Unit will continue to send data in binary for-
mat unless an OD0 command is received.
OS
IN
OD0
OD1
ID0
ID1
Command
---
When this bit is “1”, it indicates that the transmission data is in binary
format.
occurred.
Reserved (variable signal status)
Output Status
Initialize
Output Data
(ASCII)
Output Data 1
(Binary)
Input Data 0
(ASCII)
Input Data 1
(Binary)
---
Name
BIN
Sends the Unit’s internal status to the host.
Returns the Unit to its initial settings.
After executing this command, the Unit converts
internal data to ASCII and sends the data to the host.
After executing this command, the Unit sends inter-
nal data to the host in binary format.
ASCII data from the host is converted to binary for-
mat and read into the Unit.
Data from the host is read into the Unit in binary for-
mat.
---
P.ERR
Description
C.ERR
T.ERR
Section 5-2
G.ERR
41

Related parts for CV500BSC51