PC Errors
5-4-3 Fatal Operating Errors
122
Battery error
CPU SIO set error
PWR off
(No message is displayed) A power interruption
Expans Rack OFF
CPU error
Memory error
Programming Console
Programming Console
error message
error message
Note
CPU Unit or Memory Card
backup battery is missing or its
voltage has dropped.
The registered CPU Bus Unit
number doesn’t agree with the
registered unit number.
A momentary power interruption
can be set as an non-fatal error
in the PC Setup.
longer than the
momentary power
interruption time has
occurred.
A power interruption to an
Expansion Rack has
occurred.
Watchdog timer has
exceeded maximum
setting.
An error has occurred
during check of the PC or
EM Unit memory, or
program transfer could
not be completed at
start-up.
Probable Cause
The following errors occur after program execution has been started. PC opera-
tion and program execution will stop and all outputs from the PC will be turned
OFF when any of the following errors occur.
None of the CPU Unit indicators will be lit for the power interruption error, and
only the POWER indicator will be lit for the Expansion Rack power interruption
error. The POWER and WDT indicators will be lit for the CPU Unit error. For all
other fatal operating errors, the POWER and ERROR indicators will be lit. The
RUN output will be OFF.
1. Error codes 0200 to 0215 indicate CPU Bus Units #00 to #15, respectively,
2. A424 contains the unit number of the Master involved, and A480 to A499
3. A425 contains the unit number of the Master involved, and A470 to A477
4. A42615 is turned ON to indicate a battery error, and A42614 is turned ON to
5. Error codes 0400 to 0415 indicate CPU Bus Units #00 to #15, respectively,
Probable cause
while 0231 indicates a CPU bus link error. Also, A422 contains the errant
Unit’s number, and A42315 is turned ON to indicate a CPU bus link error.
contain the unit number of the Slave involved.
contain the unit number of the Slave involved.
indicate a Memory Card battery error.
while 0431 indicates a CPU Bus Link error. Also, A427 contains the errant
Unit’s number.
None
None
None
A40115 80F1
Flag(s)
A40204 00F7
A40203 0400 to 0415
A40202 0002
Flag(s)
None
None
80FF
Error code
(A400)
or 0431
Error code
(A400)
5
Check power supply voltage and
power lines. Try to power-up again.
Turn on the power supply to the
Expansion CPU and Expansion I/O
Racks.
Turn the power OFF and restart.
Check Memory Card and EM Unit
to make sure they are mounted and
backed up properly. Perform a
Program Check Operation to locate
cause of error. If error not
correctable, try inputting program
again.
Check battery and replace if
necessary.
Check the errant Unit.
Check the power supply
voltage and lines.
Possible remedy
Possible remedy