DS6-34DSX161N0-N EATON CUTLER HAMMER, DS6-34DSX161N0-N Datasheet - Page 4

Motor Starter

DS6-34DSX161N0-N

Manufacturer Part Number
DS6-34DSX161N0-N
Description
Motor Starter
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of DS6-34DSX161N0-N

Supply Voltage Range
24 VDC
No. Of Phases
Three
Power Rating
90kW
Current Rating
161A
Operating Temperature Range
0°C To +40°C
Horsepower, 3-phase
125hp
Features
Soft Start
Horsepower, 1-phase
50hp
Instructional Leafl et IL03901001E
Effective June 2009
Control wiring
A minimum of 16 AWG should be used between the power supply
and the 24 Vdc + and – terminals.
Terminal connections are to be secured to a torque value of 3.6 lb-in.
Control wiring is connected to the DS6 soft start controller by a
9-pin terminal block located on the front of the unit. Use the wiring
diagrams in Figure 4, Figure 5, and the information in Table 7
as guides.
Figure 4. Direct Start
Table 6. Terminal Designations
4
Terminal
OV
+24
–A2
EN
+A1
13, 14
23, 24
Description
Control ground or power supply common
Plus 24 Vdc from power supply
Common with 0V, connected externally
Start command enable/stop command
Start command/ramp stop command
Top of ramp contacts—NO
Ready status contacts—NO
EATON CORPORATION www.eaton.com
0V +24
0V +24 –A2 EN +A1 13 14
Control Wiring Terminal Block
–A2 EN +A1 13 14
Q1
TOR
23
23
Ready
24
+24V
0V
24
Figure 5. Direct Start With Soft Stop
Table 7. DS6 Terminal Control Block Wiring
Name
Circuit
common
Power
–A2
Enable
+A1
Relay
Relay
Block
Designation
0V
+24
–A2
EN
+A1
13
14
23
24
0V +24
Input
Common
24 Vdc nominal (see 24 Vdc power
supply requirements) section for
sizing of power supply
Control power common
24 Vdc maintained
24 Vdc maintained
NO contact rated @ 250 Vac,
3A resistive, 1A inductive
NO contact rated @ 250 Vac,
3A resistive, 1A inductive
NO contact rated @ 250 Vac,
3A resistive, 1A inductive
NO contact rated @ 250 Vac,
3A resistive, 1A inductive
-A2 EN +A1 13 14
DS6 series soft start controllers
Q1
TOR
23
Ready
S3
+24V
0V
24
Connections
Common
+24 Vdc power from
power supply
Common
START command with
+A1 energized. Remove
for STOP command
START command
with EN energized.
Remove for STOP
RAMP command
Top of ramp signal–
in bypass
Top of ramp signal–
in bypass
READY status signal
READY status signal

Related parts for DS6-34DSX161N0-N