S701G25N3S EATON CUTLER HAMMER, S701G25N3S Datasheet - Page 22

Motor Starter

S701G25N3S

Manufacturer Part Number
S701G25N3S
Description
Motor Starter
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of S701G25N3S

No. Of Phases
Three
Power Rating
20hp
Current Rating
25A
Peak Reflow Compatible (260 C)
No
Output Current
25A
Supply Voltage Max
600VAC
Control Voltage Max
300V
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39.1
DS6 Soft Start kW Ratings
Please refer to Application Note AP03900001E for additional information
on proper size selection.
DS6 25–75 hp Model
DS6 100–150 hp Model
22
Control Products Catalog CA08102001E—September 2010 www.eaton.com
DS6 Soft Start Controllers—kW Ratings According to IEC 60947-4-2—
10 Second Ramp, 1 Start per Hour, 300% Current Limit at 40°C
Rated
Current (A)
41
55
68
81
99
134
160
196
10 Second Ramp, 1 Start per Hour, 400% Current Limit at 40°C
Rated
Current (A)
28.8
37.5
46
56
68
90
106
134
Considerations
1. Either XTOB, C306 or C440 series or equivalent overload protection devices may be selected.
2. Contactor is optional for normal applications. It is recommended for mains isolation.
Power Supply
Eaton’s PSG and ELC power supplies are recommended as a compact and low-cost
source for 24 Vdc power The light-weight, DIN rail mounted devices have a wide input
voltage range, and robust screw terminals make these power supplies easy to install
and use. These power supplies are available in 1A and 2A models.
Power Supply Selection
Description
85–264V input and 24V output
380–480V input and 24V output
100–240 Vac input and 24 Vdc output
380–480 Vac input and 24 Vdc output
Notes
Maximum values may be higher than allowed per NEC 430.52 and UL 508A 31.1.
XTOBXDIND Panel Mounting Adapter must be used with this overload.
XTOBXTLL line and load lugs must be used with this overload.
ZEB-XCT300 current transformer must be used with this overload.
Reduced Voltage Motor Starters
Solid-State Controllers
Motor Power (kW)
230V
11
15
15
22
30
30
45
55
Motor Power (kW)
230V
7.5
11
11
15
18.5
22
30
37
400V
22
30
37
45
55
75
90
110
400V
11
18.5
22
30
37
45
55
75
Maximum
Allowable
Breaker Size
HFD3150L
HFD3200L
HJD3250
HKD3300
HKD3350
HKD3400
HLD3450
HLD3500
Maximum
Allowable
Breaker Size
HFD3150L
HFD3200L
HJD3250
HKD3300
HKD3350
HKD3350
HLD3450
HLD3500
Catalog Number
ELC-PS01
PSS25F
PSG60E
PSG60F
Maximum
Allowable
Fuse Size
150A Class RK5
200A Class RK5
200A Class RK5
300A Class RK5
350A Class RK5
500A Class RK5
500A Class RK5
500A Class RK5
Maximum
Allowable
Fuse Size
150A Class RK5
200A Class RK5
200A Class RK5
300A Class RK5
350A Class RK5
500A Class RK5
500A Class RK5
500A Class RK5
Recommended
XTOB Overload
XTOB057DC1
XTOB057DC1
XTOB070GC1
XTOB100GC1S
XTOB100GC1S
XTOB150GC1S
XTOB160LC1
XTOB220LC1
Recommended
XTOB Overload
XTOB040DC1
XTOB040DC1
XTOB057DC1
XTOB065DC1
XTOB100GC1S
XTOB100GC1S
XTOB160LC1
XTOB160LC1
Recommended
C440 Overload
C440A1A045SAX
C440B1A100SAX
C440B1A100SAX
C440B1A100SAX
C440B1A100SAX
C440A1A005SAX
C440A1A005SAX
C440A1A005SAX
Recommended
C440 Overload
C440A1A045SAX
C440A1A045SAX
C440B1A100SAX
C440B1A100SAX
C440B1A100SAX
C440B1A100SAX
C440A1A005SAX
C440A1A005SAX
Catalog Number
DS6-34DSX041N0-N
DS6-34DSX055N0-N
DS6-34DSX068N0-N
DS6-34DSX081N0-N
DS6-34DSX099N0-N
DS6-34DSX134N0-N
DS6-34DSX161N0-N
DS6-34DSX196N0-N
Catalog Number
DS6-34DSX041NO-N
DS6-34DSX055NO-N
DS6-34DSX068NO-N
DS6-34DSX081NO-N
DS6-34DSX099NO-N
DS6-34DSX134NO-N
DS6-34DSX161NO-N
DS6-34DSX196NO-N

Related parts for S701G25N3S