Device Monitor Function
Reference:
S Monitoring will stop in the row while the popup input window is being dis-
S No other operations can be performed while the popup input window is being
When the input window is displayed, the binary PV cell will change as shown
below to receive the new hexadecimal PV.
NT31/NT31C:
“From > jjjj To > ????”
NT631/NT631C:
“From > jjjj To > ????”
• The jjjj field shows the original PV that was displayed when the hexade-
• The ???? field displays the new PV as it is entered.
Changing a Word PV
Input the new PV by pressing the hexadecimal touch switches (0 to 9 and A to F)
on the popup input window. Each time that a digit is pressed, it will appear in the
???? field in the binary PV table cell. The digits are input from right to left.
The following values will be displayed as the five keys 3 → 5 → C → 8 → A are
pressed: 0003 → 0035 → 035C → 35C8 → 5C8A.
The new PV field can be returned to 0000 by pressing clear.
Force-setting and Force-resetting Timer/Counter Completion Flags
Specify force-setting or force-resetting by pressing the corresponding touch
switch in the popup input window.
Clearing a Timer/Counter’s Forced Status
Specify clearing the forced status by pressing the corresponding touch switch in
the popup input window.
If the Clear touch switch is pressed, the force-clear operation will be cancelled
and the PV will be returned to its previous value.
Force-setting
Force-resetting
Clearing forced
status
2. Input the new word PV or specify the timer/counter’s new forced status.
3. Press the Write touch switch. The new value will be written to the word in the
played. Monitoring will continue in the other rows and any changes in those
words will appear on the screen.
displayed on the screen. (The PT can be controlled from the PC if the PT is
operating.)
cimal PV table cell was pressed.
specified row, the hexadecimal PV, binary PV, and PV character will change
to match the new value, and the PT will restart monitoring. At the same time,
the popup input window will be closed.
If the new value cannot be written, an error message will be displayed in the
lower-left corner of the screen and the buzzer will sound. (This buzzer sound
can be disabled with the PT’s touch switch sound setting.) In this case,
check the status of the PC and specified data area and try changing the val-
ue again. The error message will be cleared when the data is written proper-
ly.
Action
Action
Set or Force-set
Reset or Force-reset
Release or Force-release
Touch switch
Touch switch
SET
RESET
Clearing force-set status:
PV (0000)
Clearing force-reset status:
PV before force-reset
Display after change
Display after change
Section
2-17