RS485-M850 HOBUT, RS485-M850 Datasheet

no-image

RS485-M850

Manufacturer Part Number
RS485-M850
Description
MODULE, RS485, FOR USE WITH M850
Manufacturer
HOBUT
Datasheet

Specifications of RS485-M850

Accessory Type
RS485
Svhc
No SVHC (15-Dec-2010)
For Use With
M850
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
M850 MULTIFUNCTION
METERS
DESCRIPTION
The new range of Hobut multifunction panel meters
feature 96 x 96mm sizes complete with unique blue
LED screen, which can be seen in direct sunlight. The
range is easy to use, features user-programmable CT &
VT ratios, and can be used on any single or 3 phase
system with any input voltage without re-programming.
APPLICATION
The range is a cost effective replacement for traditional
panel meters and is suitable for low, medium and high
voltage control panels, gensets, building management
systems, power management and more.
STANDARD FUNCTIONS:
Phase Voltage (V)
Phase to Neutral Voltage (V)
Phase Current (I)
Frequency (Hz)
Active Power (W)
Active Energy (kWh)
Reactive Power (VAr)
Apparent Power (VA)
Reactive Energy (VArh)
All models feature the
following user-programmable
functions:
• Current Transformer Ratio
• Voltage Transformer Ratio
• Baud Rate, Parity, Stops
Both pulsed output
(for Wh or VArh) and
RS 485 output
(Modbus protocol)
are plug in options
which can be
supplied with the
multifunction meter.
If purchased
separately please use
ordering codes on
right.
RANGE
PROGRAMMABLE FUNCTIONS
PLUG-IN OPTIONS
Power Factor (PF)
Instantaneous Amp Demand
Instantaneous Watt Demand
Instantaneous VA Demand
Maximum Amp Demand
Maximum Watt Demand
Maximum VA Demand
Neutral Current Measurement
• AC or DC AUX
• 1A or 5A CT
• Single or 3 phase system
• Input voltage range 28-570V
• RS485 address, 1-247
• Security code access for
programming
Suitable for any 1 or 3 phase
system, AC aux 100-440V or
DC aux 100-420V
Input 28/330V L-N
Pulsed Output
RS 485 Output
1A input (instead of 5A)
330mV Input
(instead of 1A or 5A CT)
Order example: a standard product with RS 485 output is part
ORDERING INFORMATION
STANDARD PRODUCT
48/570V L-L
5A
M850-MP1
when ordered separately
use part PULSE-M850
number M850-MP1-RS
Pulsed Output
P
OPTIONAL EXTRAS
when ordered separately
use part RS485-M850
RS
RS 485 Output
1
MV

Related parts for RS485-M850

RS485-M850 Summary of contents

Page 1

... Input 28/330V L-N 48/570V L-L 5A Pulsed Output RS 485 Output 1A input (instead of 5A) 330mV Input (instead CT) Order example: a standard product with RS 485 output is part number M850-MP1-RS Pulsed Output when ordered separately use part PULSE-M850 485 Output when ordered separately use part RS485-M850 ...

Page 2

... E-mail: sales@hobut.co.uk Web: www.hobut.co.uk 3kV RMS 50Hz for 1 minute between case, input and aux. 1kV between case, input, aux, relay output & RS485 output. EMC 5kV transient complies with IEC801/ EN55020 HF EHF 2.5kV 1Mhz complying to IEC255-4 DIN57411 / VDE IEC688, BSEN60688, BS4889, IEC359 ...

Related keywords