MODEL BMK9 - DIN RAIL MOUNT ADAPTER KIT FOR PAX
INSTALLATION
1. Remove the panel latch (mounting clip) from the PAX meter unit and insert
2. The PAX meter may be wired after the unit has been mounted in the adapter
3. Slide the PAX meter through the cut out in the BMK9 and then slide
4. Continue sliding the PAX meter until the bezel flange contacts
5. Slide the panel latch (mounting clip) towards the front of the
6. Alternately tighten mounting screws through the rear access holes of the
7. Apply both DIN rail feet to the rear of the adapter frame. The two latching
8. Wire PAX meter appropriately.
9. To install the complete assembly on a T style rail, angle the assembly so that
10. To remove the assembly from the rail, place a screwdriver behind the
DIMENSIONS In inches (mm)
the mounting screws (supplied with the PAX) on both sides of panel latch.
The tip of the screw should not project from the hole in the panel latch
(mounting clip).
frame, in which case continue with Step 3. If pre-wiring the PAX is more
convenient, skip to the pre-wiring step at the end of this installation
procedure before returning to Step 3.
the panel latch (mounting clip) over the rear of the PAX.
the adapter frame. The PAX panel gasket is optional.
unit until it latches firmly against the inside of the adapter
frame. Note: It is necessary to hold the PAX meter in place
when sliding the mounting clip into position.
adapter frame.
pins of the rail foot are positioned into the mating holes on the adapter
frame. Slight pressure applied to the center of the rail foot will snap foot into
locking position.
the top groove of both rail feet are located over the top lip of the rail. Push
the assembly towards the rail until it snaps into place.
bottom groove of the foot rail and slightly pry upwards to release first rail
foot. Apply same procedure to second rail foot and remove complete
assembly.
DESCRIPTION
to DIN rail mount requirements. Wire feed to the PAX unit may be through the top
or bottom of the adapter kit.
and includes two plastic DIN rail mounting feet for attachment to a top hat (T)
profile rail according to EN50022 - 35 x 7.5 and 35 x 15.
Pre-wire PAX
2a. Route wires through the panel latch (mounting clip) and then through the
The BMK9 DIN rail mount kit is designed to adapt any PAX panel mount meter
The DIN rail adapter frame is constructed of steel with a textured black finish
front cut out of the adapter frame from the inside to the outside. Wire PAX
meter appropriately. Continue with installation at Step 3 above.
ORDERING INFORMATION
For More information on Pricing, Enclosures & Panel Mount Kits
refer to the RLC Catalog or contact your local RLC Distributor.
MODEL NO.
BMK9
DESCRIPTION
DIN Rail PAX Base Mount Kit
Bulletin No. BMK9-X
Drawing No. LP0608
Effective 4/05
PART NUMBER
BMK90000