Page 1
... MCR-VDC-UI-B-DC Voltage Transducer for DC Voltages INTERFACE Data Sheet 100260_en_01 1 Description The MCR voltage transducer measures DC voltages in several signal ranges from 0 ... ± ... ±660 V DC and converts them to standardized analog signals. DC voltages can be processed with both positive and negative polarity. The input voltage ranges listed at input terminal blocks can be varied by ± ...
Page 2
... V DC (36 kΩ) ± (24 kΩ) ±660 V DC (not grounded) ±100 V DC (to ground) -10 V ... 10 V ±15 V > 10 kΩ < -20 mA ... 20 mA ±30 mA < 500 Ω < 18 ... 30 < True r.m.s. value measurement < 1% (of final value) < 0.015%/K ±20% ±20 IP20 MCR-VDC-UI-B-DC Pcs./Pck PHOENIX CONTACT ...
Page 3
... According to EN 50178 1.5 kV (50 Hz, 1 min.) II -25°C ... +50°C CE-compliant u EN 61000-4 air discharge EN 61000-4-3 10 V/m 10 V/m EN 61000-4-4 Input/output/supply: 2 kV/5 kHz Input/output: 2 kV/42 Ω EN 61000-4-5 Supply: 0.5 kV/2 Ω EN 61000-4-6 Input/output/supply 55011 Class A MCR-VDC-UI-B-DC 3 PHOENIX CONTACT ...
Page 4
... DIN rails according to EN 60715. Install the module in suitable housing to meet the requirements for the protection class. Screw Connection Insert the wires in the corresponding connection terminal block. Use a screwdriver to tighten the screw in the opening above the connection terminal block MCR-VDC-UI-B- ...
Page 5
... Close the housing again until it engages with a click Carry out a ZERO/SPAN adjustment each time the input or output range is changed ± 1 ± 2 ± Jumper/ Setting J1/setting 1 J1/setting 2 J1/setting 3 (default setting) MCR-VDC-UI-B-DC 54V HYBRID TV1 36V 24V PHOENIX J CONTACT 1 54V 2 36V 3 24V PHOENIX CONTACT 5 ...
Page 6
... Current output (0 … ±20 mA): I Final Value Adjustment (SPAN) Use the calibration device to specify the maximum voltage used within the input voltage range (see "Selecting the Input Voltage Range" on page 5). Set the output signal value (U OUT mA) using the SPAN potentiometer. OUT MCR-VDC-UI-B- OUT = 0 mA OUT = ...