MCR-C-UI-UI-DCI-NC Phoenix Contact, MCR-C-UI-UI-DCI-NC Datasheet

no-image

MCR-C-UI-UI-DCI-NC

Manufacturer Part Number
MCR-C-UI-UI-DCI-NC
Description
INTERFACE ANALOG
Manufacturer
Phoenix Contact
Datasheet

Specifications of MCR-C-UI-UI-DCI-NC

Input Type
Configurable
Output Type
Configurable
No. Of Output Channels
1
Accuracy
± 0.1%
Supply Voltage Range
18VDC To 30VDC
Approval Bodies
CE, GL, UL Recognised
External Depth
114.5mm
External Length /
RoHS Compliant
External Length / Height
99mm
Rohs Compliant
Yes
Signal Conditioner Input
0V To 10V
Signal Conditioner Output
0V To 10V
MCR-C-UI-UI(-450)-DCI(-NC)
3-way isolation amplifier
INTERFACE
Data Sheet
100238_en_02
Description
The MCR-C-UI-UI(-450)-DCI(-NC) 3-way isolation amplifier
is used to electrically isolate and convert analog signals. The
device provides electrical isolation of analog standard sig-
nals. The module input and output are supplied via integra-
ted DC/DC converters, which are electrically isolated from
the mains (3-way isolation).
The required auxiliary voltage is indicated via a green power
LED. This clearly indicates whether or not auxiliary voltage is
available.
The MCR module ensures the safe decoupling of a sensor
circuit from the evaluation circuit and also prevents the nega-
tive effects of several sensor circuits connected with one
another. 3-way isolation enables the universal use of modu-
les both locally and close to the control system for signal con-
version and electrical isolation, as well as on the transmis-
sion path for jumpering high load resistors.
Signals are converted by an inductive transmission method.
In addition, a filter connected downstream of the transmitter
reduces possible interference.
WARNING: Correct usage in potentially explosive areas
The module is a category 3 item of electrical equipment. Follow the instructions provided here during instal-
lation and observe the safety instructions.
Make sure you always use the the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf
This data sheet is valid for all products listed on the following page:
© PHOENIX CONTACT - 01/2008
Features
Configurable 3-way isolating amplifiers
Input and output signal range can be configured via DIP
switches
ZERO/SPAN adjustment using potentiometers
Can be supplied configured or unconfigured

Related parts for MCR-C-UI-UI-DCI-NC

MCR-C-UI-UI-DCI-NC Summary of contents

Page 1

... The required auxiliary voltage is indicated via a green power LED. This clearly indicates whether or not auxiliary voltage is available. The MCR module ensures the safe decoupling of a sensor circuit from the evaluation circuit and also prevents the nega- tive effects of several sensor circuits connected with one another ...

Page 2

... ±2 ± ± ± ... ... ... ± ± ± ... ... 100238_en_02 Type MCR-C-UI-UI-DCI MCR-C-UI-UI-450-DCI MCR-C-UI-UI-DCI-NC Input IN03 IN18 -1 ... +1 V IN28 0 ... 500 IN19 -2 ... +2 V IN29 0 ... IN20 -2.5 ... +2.5 V IN30 0 ... IN21 -5 ... +5 V IN31 0 ... 2 IN22 -10 ... +10 V IN32 0 ... IN23 -20 ... +20 V IN33 -5 ... + ... 60 mV IN34 -10 ... +10 mA OUT14 = = IN25 0 ...

Page 3

... Load/output load voltage output Load/output load current output Power supply Supply voltage range Max. current consumption General data Limit frequency (3 dB) MCR-C-UI-UI-DCI MCR-C-UI-UI-DCI-NC Limit frequency (3 dB) MCR-C-UI-UI-450-DCI Measuring principle Transmission error, max. Maximum temperature coefficient Alignment zero Alignment span Step response (10-90%) ...

Page 4

... GND 1 100238_en_02 1.5 kV (50 Hz, 1 min (50 Hz, 1 min.) -20 °C ... 65 °C CE compliant Class I, Div. 2, Groups non-hazardous locations Germanischer Lloyd EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 55011 OUT OUT U GND 2 9 +24V DC 10 GND 3 11 GND 3 12 MCR-C-UI-UI(-450)-DCI(-NC) Class A 4 PHOENIX CONTACT ...

Page 5

... CAUTION: Electrostatic discharge The module contains components that can be damaged or destroyed by electrostatic discharge. When hand- ling the module, observe the necessary safety precautions against electrostatic discharge (ESD) according to EN 61340-5-1 and EN 61340-5-2. 100238_en_02 MCR-C-UI-UI(-450)-DCI(-NC) 5 PHOENIX CONTACT ...

Page 6

... The current measuring transducer is connected to the power supply at the "+24VDC" and "GND" connection terminal blocks (see block diagram). 100238_en_02 DIP switches S1 and S2 are located inside the housing Supply voltage 2 Output: Standard signals 1 3 "ZERO" and "SPAN" potentiometers 4 "POWER" LED 5 Input: Standard signals 6 Universal snap-on foot for EN DIN rails MCR-C-UI-UI(-450)-DCI(-NC) 6 PHOENIX CONTACT ...

Page 7

... Insert the wires in the corresponding connection terminal block. Use a screwdriver to tighten the screw in the opening above the connection terminal block MCR-C-UI-UI(-450)-DCI(-NC) WARNING In potentially explosive areas, snap the modu- le onto the DIN rail and connect the cables only when the power is disconnected. PHOENIX CONTACT 7 ...

Page 8

... Both potentiometers are located on the top of the module. ATTENTION: Module can become damaged Before commencing the adjustment process, observe the warm-up phase of two minutes. MCR-C-UI-UI(-450)-DCI(-NC) 8 PHOENIX CONTACT ...

Page 9

... Output final value 5 V Adjustment tolerance ±0.5 mV 100238_en_02 0 ... 10 V Output DIP 2 DIP ... 5 mA Output 0 ... 10 mA Output DIP 2 DIP ±10 V Output 1 ... 5 V Output ±0.5 mV ±1 mV MCR-C-UI-UI(-450)-DCI(-NC) ±5 V Output ±10 V Output DIP ... 20 mA Output DIP ... 20 mA Output 4 ... 20 mA Output ±1 μA ±1 μA ...

Page 10

... Specifying the Input Signal Range via DIP Switch 1 Specifying the Output Signal Range via DIP Switch 2 100238_en_02 MCR-C-UI-UI(-450)-DCI(-NC) Select one of the possible signal ranges using the appropri- ate configuration of DIP switch 1 according to the table. Exception: Bipolar input signals are not permitted for the 4 … ...

Page 11

... MCR-C-UI-UI(-450)-DCI(-NC) Output With Adjustment Point Calculation (±5 V/± ... 5 V/0 ... 5 mA/0 ... 10 mA/0 ... 20 mA/4 ... 20 mA) Set the output range via DIP switch 2. Please note the selec- ted input range. Specify the initial and final value of the input signal using a calibration device. ...

Page 12

... Level sensor 0...20mA 24V Application example: Level measurement PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany 100238_en_02 MCR-C-UI-UI-DCI 1 U/I 2 GND 1 3 GND 1 Phone: +49-(0) 5235-3-00 • Fax: +49-(0) 5235-3 www.phoenixcontact.com MCR-C-UI-UI(-450)-DCI(-NC) OUT POWER (+) 24V GND 3 24V 9 12 ...