E5GN-R1P AC100-240 Omron, E5GN-R1P AC100-240 Datasheet - Page 8

no-image

E5GN-R1P AC100-240

Manufacturer Part Number
E5GN-R1P AC100-240
Description
TEMPERATURE CONTROLLER
Manufacturer
Omron
Series
E5GNr
Type
Temperature Controller, Digitalr
Datasheet

Specifications of E5GN-R1P AC100-240

Input Type
RTD
Controller Type
On/Off or Proportional (PID)
Temperature Range
Selectable, Varies By Input Type
Output Type
Relay
Supply Voltage
100 ~ 240VAC
Size
48mm W x 24mm H (1/32 DIN)
Features
NEMA 4X, IP66
Display Type
4 Digit (2)
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Communications
-
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
E5GN-R1PAC100-240
E5GNR1PAC100240
Nomenclature
8
Operation Indicators
1. AL (alarm)
Lights when alarm output is ON.
2. CMW (communications writing control)
Lights when communications writing is
enabled and is out when it is disabled.
3. STP (stop)
Lights when control of the E5GN has
been stopped.
During control, this indicator lights when
an event or the run/stop function has been
stopped. Otherwise, this indicator is out.
4. OUT (control output)
Lights when control output is ON.
Digital Temperature Controllers
Level Key
Press this key to select the setup level. The
setup level is selected in order "operation level"
"adjustment level," "initial setting level"
"communications setting level."
Temperature Unit
The temperature unit is displayed when the dis-
play unit parameter is set to a temperature. In-
dication is determined by the currently selected
"temperature unit" parameter set value. When
this parameter is set to " C," "c" is displayed,
and when set to " F," "f" is displayed.
E5GN
Mode Key
Press this key to select parameters
within each level.
No. 1 Display
Displays the process value or parameter type.
No. 2 Display
Displays the set point, manipulated variable or
set value (setup) of the parameter.
Up Key
Each press of this key increases values displayed on
the No.2 display. Holding down this key continuously
increases values.
Down Key
Each press of this key decreases values displayed on
the No.2 display. Holding down this key continuously
decreases values.
Level + Mode Key
This key combination sets the E5GN to the
"protect level."

Related parts for E5GN-R1P AC100-240