VZA40P4BAA Omron, VZA40P4BAA Datasheet - Page 9

INVERTER DRIVE, 0.55KW, 400VAC

VZA40P4BAA

Manufacturer Part Number
VZA40P4BAA
Description
INVERTER DRIVE, 0.55KW, 400VAC
Manufacturer
Omron
Datasheet

Specifications of VZA40P4BAA

Supply Voltage Range
380VAC To 480VAC
No. Of Phases
Three
Power Rating
0.55kW
Output Voltage Max
480V
Frequency Range
57Hz To 63Hz
Svhc
No SVHC (15-Dec-2010)
Approval Bodies
CE, CUL, TUV, UL
External Depth
99mm
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Standard connections
Installation
V1000
Multi- function pulse / analog inputs
Supply
Power
(default: frequency reference)
(default setting)
L2
L1
L3
Multi-function
digital inputs
Safe Disable
Switch
Main
inputs
power supply use
R/L1 and S/L2
Fuses
For 1-phase
Forward/Stop
Reverse/Stop
External Fault
Fault Reset
Multi-speed 1
Multi-speed 2
2 kΩ
Symbols:
Filter
Use twisted pair cables
Use shielded twisted pair cables
+V
A1
AC
HC
SC
RP
A2
H2
H1
S1
S2
S3
S4
S5
S6
R/L1
S/L2
T/L3
+2
DIP
switch S3
Shielded ground
terminal
Pulse Input
(max. 32kHz)
Analog input power supply
+10.5 VDC, max. 20 mA
Multi-function analog input 1
0 to 10 V (20 k Ω )
Multi-function analog input 2
0 to 10 V (20 k Ω ) or
0/4 to 20 mA (250 Ω )
DC reactor
(option)
Link
Terminal resistance
(120 Ω , 1/2 W)
V1000
+1
+24 V 8 mA
SOURCE
SINK
0 V
24 V
Thermal
relay
B1
Indicates a main circuit terminal
Indicates a control circuit terminal.
B2
Braking
resistor
(opt)
U/T1
V/T2
W/T3
MP
AM
AC
MA
MB
MC
P1
P2
PC
R+
R−
S+
S−
IG
Fault
Pulse train output
(max. 32 kHz)
(Output frequency)
Ground
Photocoupler
common
Frequency agree
During run
Analog output
0 to +10 VDC (2mA)
(Output frequency)
Shielded
Cable
Multi-function relay output
250 Vac / 30 VDC (10 mA to 1A)
(default setting)
U
W
V
Memobus comm.
RS-485/422
max. 115 kBps
M
Multi-function photo-
coupler output
48 VDC, max. 50 mA
(default setting)
Monitor outputs
(default setting)
9

Related parts for VZA40P4BAA