AFCM0000 Red Lion Controls, AFCM0000 Datasheet

no-image

AFCM0000

Manufacturer Part Number
AFCM0000
Description
6MM ANALOG-FREQ CONVERTE
Manufacturer
Red Lion Controls
Datasheet

Specifications of AFCM0000

Rohs Compliant
NA
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
DESCRIPTION
standard signals to frequency signals or pulse width modulated (PWM) signals.
Input signal ranges are 0 - 20 mA, 4 - 20 mA, 0 - 10 mA, 2 - 10 mA,
0 - 10 V, 2 - 10 V, 0 - 5 V, or 1 - 5 V.
following parameters to be configured:
MODEL AFCM - ANALOG TO FREQUENCY CONVERTER MODULE
ORDERING INFORMATION
MODEL NO.
DIMENSIONS In inches (mm)
The configurable analog to frequency converter is used to convert analog
The DIP switches are accessible on the side of the housing and allow the
– Input signal
– Output values
– Output type (frequency or PWM)
– Filter type (for smoothing interferences on the input signal)
– Input over/under range fault detection
AFCM
DESCRIPTION
Analog to Frequency Converter Module
PART NUMBER
AFCM0000
SAFETY SUMMARY
The corresponding national regulations must be observed.
SPECIFICATIONS
INPUT
1. INPUT SIGNAL RANGE (Configurable): 0 - 20 mA, 4 - 20 mA,
2. MAX. INPUT SIGNAL:
3. INPUT RESISTANCE:
OUTPUT
1. OUTPUT SIGNAL RANGE (Configurable):
2. MIN. LOAD:
3. MAX. LOAD CURRENT: 20 mA
4. OUTPUT: NPN open collector transistor
5. MAX. SWITCHING VOLTAGE: 30 V
6. OVER-RANGE/UNDER-RANGE FAULT DETECTION: Configurable
7. OUTPUT PROTECTION: Short circuit and polarity protection
GENERAL DATA
1. SUPPLY VOLTAGE: 19.2 - 30 VDC
2. NOMINAL VOLTAGE: 24 VDC
3. CURRENT CONSUMPTION: < 10 mA
4. POWER CONSUMPTION: < 200 mW
5. TRANSMISSION ERROR: < 0.1%
6. TEMPERATURE COEFFICIENT (MAX.): < 0.02%/K
7. STEP RESPONSE:
8. TEST VOLTAGE (INPUT / OUTPUT / SUPPLY): 1.5 kV, 50 Hz, 1 min
9. AMBIENT TEMPERATURE RANGE:
10. FAULT DETECTION: Red LED under clear cover top
The device may only be installed and put into operation by qualified personnel.
0 - 10 mA, 2 - 10 mA, 0 - 10 V, 2 - 10 V, 0 - 5 V, 1 - 5 V
Current inputs: 100 mA
Voltage inputs: 30 VDC
Current inputs: 50 Ω, approx.
Voltage inputs: 110 KΩ, approx.
Frequencies: 0 - 10 kHz, 0 - 5 kHz, 0 – 2.5 kHz, 0 - 1 kHz, 0 - 500 Hz 0 -
PWM: 7.8 kHz, 3.9 kHz, 1.9 kHz, 977 Hz, 488 Hz, 244 Hz, 122 Hz, 61 Hz
Frequency: 6 KΩ
PWM: 2 KΩ
0% to 99%: < 15 msec + (1/T)
With Largest Filter: < 1 sec + (1/T)
Operation: -20 t +65°C (-4 to 148°F)
Storage: -40 to +85°C (-4 to 183°F)
SELECTED VIA DIP SWITCH SETTINGS
VOLTAGE/CURRENT TO FREQUENCY CONVERTER
3-WAY ISOLATION OF INPUT / OUTPUT SIGNALS
UNIVERSAL CONVERSION MODULE - INPUTS AND OUTPUTS
ULTRA SLIM DESIGN – ONLY 0.244" WIDE
19 to 30 VDC POWER
installationand operation of the unit.
250 Hz, 0 - 100 Hz, 0 - 50 Hz
Read complete instructions prior to
CAUTION: Risk of Danger.
UL Recognized Component,
File # E257265
CAUTION: Risk of electric shock.
Bulletin No. AFCM-A
Drawing No. LP0665
Released 7/07

Related parts for AFCM0000

AFCM0000 Summary of contents

Page 1

... TEMPERATURE COEFFICIENT (MAX.): < 0.02%/K 7. STEP RESPONSE: PART NUMBER 0% to 99%: < 15 msec + (1/T) With Largest Filter: < 1 sec + (1/T) AFCM0000 8. TEST VOLTAGE (INPUT / OUTPUT / SUPPLY): 1.5 kV, 50 Hz, 1 min 9. AMBIENT TEMPERATURE RANGE: Operation: -20 t +65°C (-4 to 148°F) Storage: -40 to +85°C (-4 to 183°F) 10 ...

Page 2

CERTIFICATIONS AND COMPLIANCES: Conformance With EMC Guideline 89/336/EEC And Low Voltage Directive 73/23/EEC Immunity to Interference According to EN 61000-6-2 Discharge of static electricity (ESD) EN 61000-4-2 Electromagnetic HF field EN 61000-4-3 Fast transients (Burst) EN 61000-4-4 Surge voltage ...

Related keywords