SNUB0000 Red Lion Controls, SNUB0000 Datasheet - Page 2

no-image

SNUB0000

Manufacturer Part Number
SNUB0000
Description
R-C Snubber Inductive Load Suppressor
Manufacturer
Red Lion Controls
Type
Single-Phaser
Datasheets

Specifications of SNUB0000

Dimensions
19mmL×8.5mmW×23mmH
Primary Type
Surge Suppressor
Termination
Solder
Voltage, Operating
250 VAC/VDC
Wire Size
20 AWG
Rohs Compliant
Yes
No. Of Outlets
1
Voltage Rating
250V
Suppressor Type
RC Snubber
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With
Industrial Equipment
R-C SNUBBER NOISE AND ARC SUPPRESSOR
SPECIFICATIONS
1. R-C Value: 0.1 µf, 47
2. Max. Line Voltage: 250 V rms or 250 VDC
3. Frequency: DC to 62 Hz
4. Peak Pulse Voltage: 1200 V max.
ORDERING INFORMATION
APPLICATION
MODEL NO.
UL recognized component
below. Placing the suppressor across the contact in many cases can work
as well, but for maximum effect, it is best to place the suppressor directly
SNUB
(Okaya Electric America, Inc. PN# XEB0471, UL-1414, File # E47474)
The R-C snubber inductive load suppressor should be applied as shown
R-C Snubber Inductive Load Suppressor
Preferred Application
1/2 Watt (±30%)
DESCRIPTION
PART NUMBER
SNUB0000
GENERAL DESCRIPTION
solenoids or relay coils. High energy noise spikes are generated whenever
current is interrupted through an inductive load. These noise spikes may
interfere with associated equipment causing erratic operation and may also
accelerate relay contact wear. Applied across an inductive load, the R-C
snubber suppresses the noise spikes and extends contact life.
DIMENSIONS In inches (mm)
[All Dimensions are nominal]
across the load. All inductive loads in a system should be suppressed in
this manner to avoid mutual interference. The suppressors are effective in
both AC and DC circuits.
The R-C Snubber is intended to suppress the “inductive kick” from motors,
*
Use a snubber across all contacts in the load circuit.
Alternate Application
Bulletin No. SNUB-A
Drawing No. LP0349
Released 12/02