ESPTN/BX FURSE, ESPTN/BX Datasheet

LIGHTNING BARRIER, TEL LINE

ESPTN/BX

Manufacturer Part Number
ESPTN/BX
Description
LIGHTNING BARRIER, TEL LINE
Manufacturer
FURSE
Series
ESP TNr
Datasheet

Specifications of ESPTN/BX

Suppressor Type
Data Line
Output Current
300mA
Peak Surge Current
10kA
Response Time
10ns
Connector Type
Screw Terminal
Approval Category
NS/G/1235/W/100025
Clamping Voltage Vc
RoHS Compliant
Clamping Voltage Vc Max
200V
Rohs Compliant
NA
Bandwidth
15MHz
D/BX Series
Based on the ESP D Series and ESP TN, these protectors are ready-
boxed to IP66 for use in damp or dirty environments. Suitable for
most twisted pair signalling applications. Available for working
voltages of up to 6, 15, 30, 50 and 110 volts and telephone lines
with a maximum working or ringing voltage of 296 volts
Features and benefits
Electronic Systems Protection
For installation in the equipment panel, protectors which are not boxed may be more
suitable. If your system requires a protector with a very low resistance, higher current or
higher bandwidth, use the E or H Series. Unboxed protectors for 3-wire RTD systems are
available - as are plug-in protectors for telephone lines are available.
Low let-through voltage between all lines
Low in-line resistance minimises unnecessary reductions in signal
strength
Ready-boxed to IP66 and supplied ready for flat mounting
Available with screw terminals or with IDC terminals (by using /I suffix
to part number)
Colour coded terminals for quick and easy installation check –
grey for the dirty (line) end and green for clean
Screen terminal enables easy connection of cable screen to earth
Substantial earth stud to enable effective earthing
UK Oftel Approval NS/G/1235/W/100025
ESP TN/BX and ESP TN/2BX are suitable for telecommunication
applications in accordance with Telcordia and ANSI Standards (see
Application Note AN005)
Supplied as standard with screw terminals – for IDC terminals order
part code plus /I (eg ESP TN/BX/I)
Security alarm panel with ESP TN/BX (bottom) providing
protection from transient overvoltages on the dial-up
telephone line. Note how the ESP TN/BX is earthed via a
bond to the ESP 240-16A/BX (top) installed on the mains
power supply to the panel
| Twisted pair data, signal and telephone lines
Application
Use these ready-boxed protectors
on twisted pair lines in dirty or
damp environments.
For two wire lines, use /BX
versions. For four wire lines,
use /2BX versions.
Installation
Connect in series with the data
communication, signal or
telephone line either near where
it enters/leaves the building or
close to the equipment being
protected. Either way, it must be
very close to the systems earth star
point.
DIRTY
Earth
From line
internal connections. Note the colour coded,
ESP 30D/2BX with lid removed to show
grey and green, terminals
Install in series (in line)
www.furse.com
equipment
CLEAN
To