TSP 140-112 TRACOPOWER, TSP 140-112 Datasheet - Page 3

PSU, RAIL, 144W, 12V/12A

TSP 140-112

Manufacturer Part Number
TSP 140-112
Description
PSU, RAIL, 144W, 12V/12A
Manufacturer
TRACOPOWER
Datasheet

Specifications of TSP 140-112

Power Supply Type
Switch Mode
Power Supply Output Type
Fixed
No. Of Output Channels
1
Input Frequency
63Hz
Output Voltage
12V
Output Current
13A
Power Rating
156W
Input Voltage
85VAC To 132VAC / 87VAC
No. Of Outputs
1
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
http://www.tracopower.com
Input Specifications
Input voltage range
Input voltage frequency
Harmonic limits
Holdup time
Inrush current
Recommended circuit breaker,
characteristic C
or fuse, slow blow type
Efficiency
Output Specifications
Output voltage adj. range
Regulation
Ripple and Noise (20MHz Bandwidth)
Electronic short circuit protection
Output overvoltage protection
Overload protection
Overtemperature protection
Power back immunity
Status indicator
Power OK signal
– output current derating at operation below 100 VAC see graph B, page 5
– Input variation
– Load variation (10–100 %)
– trigger threshold:
– active output signal:
– relay output
(reference to –Vout)
– 24 VDC models: 24 – 28 VDC
– 48 VDC models: 48 – 56 VDC
– 24 VDC models: 35 V
– 48 VDC models: 60 V
– 24 VDC models: 35 V
– 48 VDC models: 63 V
– 24 VDC models: 18–22 V
– 36 VDC models: 27–34 V
– 48 VDC models: 36–46 V
– 24 VDC models: 22.0 V ±2.0V / 20 mA max.
– 48 VDC models: 44.0 V ±4.0V / 15mA max.
– 12 VDC models: 12 – 14 VDC
– 12 VDC models: 20 V
– 12 VDC models: 16 V
– 12 VDC models: 9–11 V
– 12 VDC models: 11.0 V ±1.0 V
– 36 VDC model: 36 – 42 VDC
– 36 VDC model: 43 V
– 36 VDC model: 48 V
– 36 VDC model: 34.0 V ±2.0V / 20 mA max.
– TSP 070/090
– TSP 070/090
– TSP 140/180
– TSP 140/180
– TSP 360
– TSP 600
– TSP 360 10.0 A
– TSP 600 15.0 A
85–132/87–264 VAC autoselect
47 – 63 Hz
EN 61000-3-2, Class A (for limited output power)
20 ms min. (full load 115/230 VAC)
115 VAC
87% typ.
At output voltage higher than nominal output voltage
max. output current has to be reduced accordingly, in
order not to exceed max. output power.
0.5 % max.
0.5 % max.
100 mV pk-pk typ. (200 mV pk-pk max. at Imax)
current limitation at Imax.
constant current, automatic recovery
electronic overload protection
switch off at overtemperature, automatic restart
dual color LED (green: DC ok, red: DC off)
(20 mA max. for TSP 070, 40 mA max. for TSP 140)
(10 mA max. for TSP 090, 20mA max. for others)
DC OK = contact closed
rated: 30 VDC/1.0 A for 12/24 VDC models
rated: 30 VDC/2.0 A for 36 VDC model
rated: 48 VDC/0.5 A for 48 VDC models
< 12 A
< 13 A
< 16 A
< 25 A
6.0 A
6.0 A
Industrial Power Supplies
TSP Series
230 VAC
< 20 A
< 25 A
< 25 A
< 30 A
90­–60­0­ Watt
Page 3 of 3