13100105 SCHROFF, 13100105 Datasheet - Page 3

PSU, RACK MODULE, 100W, 24V

13100105

Manufacturer Part Number
13100105
Description
PSU, RACK MODULE, 100W, 24V
Manufacturer
SCHROFF
Datasheet

Specifications of 13100105

Power Supply Type
Switch Mode
Power Supply Output Type
Fixed
No. Of Output Channels
1
Input Frequency
60Hz
Output Voltage
24V
Output Current
4.2A
Power Rating
101W
Input Voltage
90VAC To 254VAC /
No. Of Outputs
1
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
U
s
Signal „Output OK“
Serienschaltung
Series operation
Branchement en série
Parallelschaltung (CSB)
Parallel operation
Branchement en parallèle
PSU 1
PSU 2
MAX 103
2,7
± 0,2
V 4,5
+
+
-
-
V
V
MAX 105
1
1
± 0,25
V 11,5
MAX 112,
MAX 115
± 0,25
V 22,7
DIJM0033
DIJM0070
MAX 124
+
-
R
± 0,4
L
V
Leistungsbegrenzung
Zum Schutz des Gerätes muß der
Anwender bei Temperaturen > 50 °C
die Ausgangsleistung reduzieren.
Strombegrenzung
Die Geräte sind für Dauerkurzschluß
ausgelegt. Der Ausgangsstrom wird
begrenzt. Bei einem Kurzschluß am
Ausgang, schaltet der Ausgang ab und
versucht immer wieder neu zu starten.
Steht eine Überlast längere Zeit an,
schaltet das Netzgerät ab. Wiederan-
lauf durch Netz aus-/ einschalten.
Wird die Ausgangsspannung vom
Anwender erhöht, muß er sicherstellen,
daß der maximale Ausgangsstrom um
den gleichen Faktor verringert wird.
Beispiel: U
Überspannungsschutz (OVP)
Der OVP ist über eine zweite Regel-
schleife realisiert. Schwellen siehe
Spezifikationen.
Bei einem Fehler der OVP-Schaltung
legieren die interne Schutzdioden
durch. Diese müssen werkseitig ausge-
tauscht werden.
Serienschaltung
Sehen Sie am Ausgang externe Invers-
dioden vor. Bei Serienschaltung kön-
nen am Ausgang berührungs-
gefährliche Spannungen auftreten:
SELV-Spannung nur bis 60 V
Parallelschaltung
Zur Leistungserhöhung oder Redun-
danzbetrieb werden die Ausgänge der
Netzgeräte parallel verbunden. Es
erfolgt eine geregelte Lastaufteilung
wenn der Current Share Bus der Netz-
geräte miteinander verbunden ist (Pin
22, max. 12 Geräte parallelschaltbar,
max. Ausgangsleistung ca. 0.9*P
Damit im Redundanzbetrieb alle Netz-
geräte arbeiten ist eine Grundlast von
0,1*P
Die Entkoppeldiode ist eingebaut.
Netzspannung
Die Power Supplies haben einen Weit-
bereichseingang (90 V
Output OK Signal
Das Signal „Output OK“ zeigt an, ob die
Ausgangsspannung vorhanden ist
(siehe Diagramm Signal “Output OK“).
Garantiebedingungen
Leistungsdauer
Für dieses Produkt leisten wir 2 Jahre Garantie.
Der Anspruch beginnt mit dem Tage der
Auslieferung.
Umfang der Mängelbeseitigung
Innerhalb der Garantiezeit beseitigen wir kostenlos
alle Funktionsfehler am Produkt, die auf mangelhafte
Ausführung bzw. Materialfehler zurückzuführen sind.
Weitergehende Ansprüche – insbesondere für
Folgeschäden – sind ausgeschlossen.
Garantieausschluß
Schäden und Funktionsstörungen verursacht durch
Nichtbeachten unserer Bedienungsanleitung sowie
Fall, Stoß, Verschmutzung oder sonstige unsach-
gemäße Behandlung fallen nicht unter die Garantie-
leistung.
Die Garantie erlischt, wenn das Produkt von
unbefugter Seite geöffnet wurde. Eingriffe erfolgt
sind oder die Seriennummer am Produkt verändert
oder unkenntlich gemacht wurde.
Abwicklung des Garantieanspruches
Das vorliegende Produkt wurde sorgfältig geprüft
und eingestellt.
Bei berechtigten Beanstandungen schicken Sie uns
das Produkt bitte zurück. Zur Erhaltung Ihres
Garantieanspruches beachten Sie bitte folgendes:
Legen Sie eine möglichst genaue Beschreibung
des Defektes bei.
Das Produkt ist im Original-Karton oder gleich-
wertiger Verpackung einzusenden und zwar
versichert und portofrei.
max
erforderlich.
DC
+ 10 % => I
AC
DC
– 254 V
- 10 %.
DC
.
max.
AC
).
).
Output power limiting
In order to protect the unit, the user must
reduce the output currents at
temperatures > 50 °C.
Current limiting
The power supply features short-circuit
protection. The output current is limited .
If the overload persists, the output
voltage switches off, then keeps trying
to reset. If it persists for a long while, the
power supply switches off. Restart using
the power on/off switch.
If the output voltage is increased by the
user, the maximum output current must
be reduced by the same factor.
Example: V
Over-voltage protection (OVP)
The OVP is realized by means of an
additional loop. For thresholds, please
refer to the specifications.
If there is a fault in the OVP-circuit, the
internal fuse breaks. The fuse must be
changed
Series operation
External inverse diodes should be used
at the output. Dangerous voltages may
occur at the output with series
operation:
SELV voltage only up to 60 V
Parallel operation
The unit outputs are set up for parallel
operation to increase the output power
or for redundancy. The load share
control operates if the Current Share
Buses of the unit are linked together(Pin
22 max 12 units). max. output
performance approx. 0.9*P
all power supplies work in redundancy
mode, a basic load of 0.1*P
required.
The decoupling diode is built in.
Mains/line voltage
The power supplies have a broad
range input (90 V
Output OK Signal
The Output OK Signal is on if there is an
existing output voltage (see diagram
Signal “Output OK“).
Warranty conditions
Duration
This product has a warranty of 2 years.
The warranty begins on the day of delivery
Cover of defects
Within the warranty period Schroff will repair free of
charge any faulty functioning of the product
resulting from faulty design or defective material.
All other claims under the warranty are excluded, in
particular consequential damage.
Warranty exclusion
The warranty does not cover damage or functional
defects caused by non-adherence to the
Company´s operating instructions or such caused
by dropping, knocking, contamination or other
untoward handling. The warranty is invalidated if
the product is opened by unauthorized personnel,
tampered with or the serial number on the product
has been changed or rendered illegible.
Claims under warranty
This product has been carefully checked. If you
have a valid claim, please return the product to
SCHROFF. In order to make a claim under the
warranty, ensure that the following is carried out:
Include a detailed description of the fault.
The product should be returned in the original
carton or similar packaging, insured and
post paid.
DC
+ 10 % => I
AC
– 254 V
DC
max.
max
AC
- 10 %.
DC
).
.
So that
is
Limitation de puissance
Afin de protéger l’alimentation, l’utilisateur
doit réduire le courant de sortie si la
température est > 50 °C.
Limitation de courant
Les alimentations sont conçues pour
pouvoir supporter un court-circuit
permanent. Le courant de sortie est limité.
Si le court-circuit persiste, la tension de
sortie est coupée et essaye de
redémarrer. Si la surcharge persiste
l’alimentation se coupe. Pour redémarrer
utliser l’intérupteur.
Si l’utilisateur accroît la tension de sortie,
il doit veiller à réduire le courant maximal
de sortie dans la même proportion.
Exemple: U
Protection contre les surtensions
L’OVP est réalisée par une régulation
séparée. Voir la courbe des
caractéristiques techniques pour les
limites. S’il y a défaut sur l’OVP, les diodes
de protection sont mises en court-circuit
et doivent être remplacées en usine.
Branchement en série
Il faut prévoir des diodes de protection
contre les inversions de polarité. Lors
d’une mise en série, des tensions
dangereuses peuvent apparaître à la
sortie:
tension SELV uniquement jusqu’à 60 V
Branchement en parallèle
Pour accroitre la puissance ou pour une
utilisation en redondance des
alimentations les sorties seront reliées en
parallèle. Une répartition autonome de la
charge est assurée lorsque les sorties
Current Share Bus des alimentations sont
reliées entre elles (broche 22, max. 12
alimentations en parallèle, tension max.
de sortie env. 0.9*P
de redondance toutes les alimentations
soient en service il faut une charge
minimale de 0,1*P
La diode de découplage est intégrée.
Adaptation de la tension secteur
L´alimentation dispose d´une plage
d´entrée secteur étendue. Elle s´adapte
automatiquement à la tension secteur
(90 V
OK Signal Output
L
ou non de la tension de sortie (voir
schéma Signal “Output OK“
Garantie
Garantie contractuelle
Les conditions d‘applications de la garantie, et en
particulier la durée, l‘étendue et les cas d‘exclusion,
figurent dans nos conditions générales de ventes,
paragraphe 11 „Garantie contractuelle“.
Application de la garantie
Cette alimentation a été soigneusement contrôlée en
usine. En cas de réclamations, veuillez nous la
retourner accompagnée d‘une description la plus
précise possible du défaut constaté, et d‘une copie du
bon de livraison ou de la facture. Le produit doit nous
être retourné dans son emballage d‘origine port
assuré et payé.
Schroff n‘assume aucune responsabilité pour des
appareils non assurés et endommagés pendant le
transport.
e signal Output OK indique la présence
AC
– 254 V
DC
+ 10 % => I
AC
).
max
max
.
). Pour qu’en mode
DC
).
- 10 %.
DC
.

Related parts for 13100105